11.7
CONFIGURATION OF INPUTS AND OUTPUTS, TECHNICIAN PASSWORD: 21100
(Sub-menu 300 Input/Output)
To select sub-menu 300 and make the respective settings, after having confirmed the last page of sub-menu 200,
press key SB11 relative to the symbol
ENGLISH
and return to the choice page.
[300] Input DIG. RC
Terminals: 15 - 16
Configuration of closing of digital input
DIG0.
1) No change: OFF.
2) Enables remote control: RC.
3) Water lack: H2O MIN.
4) Max. level H2O MAX
signalling only.
5) Change SET POINT.
[301] D.O. 1
Terminals: 23 – 24 – 25
Configuration of change of RL1.
1) No change.
2) Change on Fault.
3) Pumps running
4) Water lack: H2O MIN.
signalling and blocking.
5) Max. level H2O signalling only
6) Pressure within working range.
7) Operation with pressure switches.
[302] D.O. 2
Terminals: 26 – 27 - 28
Configuration of change of RL2.
1) No change.
2) Change on Fault.
3) Pumps running
4) Water lack: H2O MIN.
signalling and blocking.
5) Max. level H2O signalling only
6) Pressure within working range.
7)
Operation with pressure switches.
[303] AN. OUT 1
Terminals: 18 - 19
Configuration of analog output 1.
1-Output: OFF.
2-Inverter frequency proportional output:
Hz.
3-Inverter current proportional output: A
[304] External reference amplification
Terminals: 17 - 18
Reference multiplication factor
H2O MIN
H2O MAX
SET P.2
Pumps ON
H2O MIN
H2O MAX
BAR=PSET
PRES-SW
Pumps ON
H2O MIN
H2O MAX
BAR=PSET
PRES-SW
1.00 - 10.00
97
Field
Default settings
OFF
OFF
RC
OFF
Fault
FAULT
RUN
OFF
OFF
FAULT
RUN
OFF
OFF
Hz
A
1