REFERENCE
Key for selecting operation of electropump three in:
-
-
SB4
Press the key
Ref. Foto 10.1
again (the led LL5A lights up).
Key for selecting electropump one in:
-
SB5
-
Ref. Photo 10.1
Key for selecting electropump two in:
-
-
SB6
Ref. Photo 10.1
Key for selecting electropump three in:
-
-
SB7
Ref. Photo 10.1
Key for:
-
SB8
-
Ref. Photo 10.1
Key for:
-
SB9
-
Ref. Photo 10.1
Key for:
-
SB10
-
Ref. Photo 10.1
Key for:
-
SB11
-
Ref. Photo 10.1
SB12
Key for accessing and leaving the help pages.
Ref. Foto 10.1
AUTO: yellow led LL5A lit: the electropump is started by the
control board.
MAN:
yellow led LL5A lit: the electropump is started by holding
down the key for more than 5 seconds. When the key is released,
the electropump stops and the led LL5A goes out.
and select automatic starting of the electropump
STOP: yellow led LL6A lit: all electropump operation is excluded.
RESET: yellow led LL6A blinking: holding down the key for more
than 5 seconds starts the reset process of the alarms that
intervened in electropump one.
STOP: yellow led LL7A lit: all electropump operation is excluded.
RESET: yellow led LL7A blinking: holding down the key for more
than 5 seconds starts the reset process of the alarms that
intervened in electropump two.
STOP: yellow led LL8A lit: all electropump operation is excluded.
RESET: yellow led LL8A blinking: holding down the key for more
than 5 seconds starts the reset process of the alarms that
intervened in electropump three.
Shifting to the left when setting the parameters and, if pressed
together with the right key, for entering the menu configuration
pages.
Decreasing the value of the selected parameter in the sub-menu.
Short press: allows access to the next parameter in the sub-menu.
Pressed for more than 2 seconds: confirms change of the
parameter.
Shifting to the right when setting the parameters and, if pressed
together with the left key, for entering the menu configuration
pages.
Increasing the value of the selected parameter in the sub-menu.
Short press: allows access to the previous parameter in the sub-
menu.
Pressed for more than 2 seconds: return to the monitor page.