ALARMS
CAUSE OF ALARM
LIST
AL5
No communication with GSM. Check state of GSM
AL6
GSM error.
AL8
Overload of motors fed by
mains:
-
Operation with inverter:
protection
panel KL1.
-
PRESSURE
operation: protection in
the
KL3
board.
AL9
Exceeded
maximum number starts
AL16
Inverter protection.
AL32
Overpressure
AL64
Lack of water, minimum level. Check minimum level or
AL 65
Maximum water level.
H2O
Minimum pressure
RESET/CHECK
modem or connecting
cable.
Ref. KL1 Local PC
Check the SIM card, credit
or network coverage.
Ref. KL5
Check motor absorption or
set
thermal
(parameters 105, 106 or
by
control
107).
On board KL3:
SWITCH
LL12 x M1
LL13 x M2
amperometric
LL14 x M3
threshold
of
Check
pumper starts, the storage
tank or the set threshold
(parameter 130).
See table INVERTER
ALARMS
TROUBLESHOOTING:
DANFOSS OR VACON
Check system pressure or
danger pressure threshold.
(parameter 122)
controls associated with it.
Ref. KL4 7-8/15-16
Check maximum level or
controls associated with it.
Ref. KL4 15-16
Check the system pressor
or the minimum set
pressure (parameter 120).
ENGLISH
IN THE SYSTEM
The pumps are
working regularly.
The pumps are
working regularly.
Three
protections
resets, manual at the
fourth attempt.
To reset, proceed as
described in chapter
11.1.
Manual reset with the
keys
amperometric board:
SB13 x M1, SB14 x
M2, SB15XM3.
the
number
of
Non blocking alarm.
It is activated if the set
number of starts is
exceeded,
when returning below
the limit.
The system continues
operating, controlled
by the transducer. The
pumps are supplied by
the mains.
The system stops.
(Automatic restart 5
seconds after pressure
returns to normal)
The system is stopped.
Check the contact
connected to terminals
7-8 or 15-16 of board
KL4.
The system continues
operating.
Check
connected to terminals
15 – 16 of board KL4
The system stops for 1
minute
Three automatic
resets, fourth attempt
alarm 64).
99
EFFECT
REMOTE ALARM
RELAY
Remote signal
Remote signal
automatic
Remote signal
No remote signal
on
the
KL3
Remote signal
it
resets
Remote signal
Remote signal
Remote signal
Remote signal
the
contact
Remote signal