iNSTallaTiON
Commissioning
Standard system with 5 m air duct (DN 200) and two 90° bends
length or
Folded spiral-seam tube
90° bend (r = 1 * d)
Intake grille
Total
f Set the fan output to 44 % in the controller menu.
f
Note
If the air duct is longer or there are more bends, perform
the following individual system calculation.
Individual system calculation
f Calculate the system pressure drop as the sum of all compo-
f
nents installed in the air duct.
f Enter the calculated pressure drop on the X-axis of the dia-
f
gram. Read off the fan output from the Y-axis and adjust the
fan output parameter in the appliance menu.
Example 1 : Air duct diameter DN 160
length or
Folded spiral-seam tube
90° bend (r = 1.5 * d)
90° bend (r = 1 * d)
Intake grille
Total
Fan graph with examples showing how to calculate the necessary fan setting with a duct connection
65
60
55
50
45
40
35
0
10
X Pressure drop [Pa]
Y Fan setting [%]
26
| SHP-F 220-300 Premium
Pressure drop per
Pressure
pce
m or per pce [Pa]
drop [Pa]
5
0.67
2
2.3
2
6.2
Pressure drop per
Pressure
pce
m or per pce [Pa]
drop [Pa]
10
2
0
4.5
3
5.5
2
6.2
20
30
40
Example 2
Example 2 : Air duct diameter DN 200
3.35
Folded spiral-seam tube
4.6
90° bend (r = 1.5 * d)
12.4
90° bend (r = 1 * d)
20.35
Intake grille
Intake expansion
Discharge reduction
Total
Table for your system
20
0
16.5
12.4
48.9
50
60
Example 1
1 Fan curve
length or
Pressure drop per
pce
m or per pce [Pa]
20
0
2
2
1
1
length or
Pressure drop per
pce
m or per pce [Pa]
70
80
90
www.stiebel-eltron.com
Pressure
drop [Pa]
0.67
13.4
2.0
0
2.3
4.6
6.2
12.4
5
5
2.8
2.8
38.2
Pressure
drop [Pa]
1
100

Publicité

Chapitres

Table des Matières