Va p o r m i s t / H u m i d i - t e c h / C R U V, s t a n d a r d w a t e r, s e r v i c e i n s t r u c t i o n s
Humidifier De-scaling Solution
Scale buildup on humidifier heaters
acts as an insulator, reducing humidifier
performance while increasing energy
costs. To keep humidifiers operating as
efficiently as possible, remove scale with
DRI-STEEM's Humidifier De-scaling Solution,
available for purchase from your DRI-STEEM
representative or distributor.
The De-scaling Solution cleans without risk
of corroding humidifier tanks or welds. The
De-scaling Solution also cleans surfaces
unreachable by hand scraping.
DRI-STEEM's Humidifier De-scaling Solution
is the only approved cleaner/de-scaler for
use with DRI-STEEM humidifiers. Use of
other cleaners/de-scalers may void your
DRI-STEEM warranty.
DRI-STEEM Corporation
An ISO 9001: 2000 certified corporation
U.S. Headquarters:
14949 Technology Drive
Eden Prairie, MN 55344
800-328-4447 or 952-949-2415
952-229-3200 (fax)
European office:
Marc Briers
Grote Hellekensstraat 54 b
B-3520 Zonhoven
Belgium
+3211823595 (voice)
+3211817948 (fax)
E-mail: marc.briers@dristeem.com
Continuous product improvement is a
policy of DRI-STEEM Corporation; therefore,
product features and specifications are
subject to change without notice.
DRI-STEEM, Vapormist, Humidi-tech, CRUV,
and Vapor-logic are registered trademarks
of DRI-STEEM Corporation and are filed for
trademark registration in Canada and the
European community.
Drane-kooler is a trademark of DRI-STEEM
Corporation.
© 2011 DRI-STEEM Corporation
Form No. VM/CRUV-standard-SKM-0711
Part No. 891000-001 Rev C
Page 6 • DRI-STEEM Vapormist/Humidi-tech/CRUV, Standard Water, Service Kit Manual
CRUV Service
1. Drain the tank. See Step 3 on page 4.
2. Clean the probes. See Step 4 on page 5.
3. Remove the tank cover and wet vac minerals out of tank
4. To remove tank for cleaning, disconnect drain line union, fill valve
5. Remove evaporating chamber and clean.
6. Install the probe and probe plug assembly. Verify that ground wire is
7. Replace tank cover, making sure tank is sealed tight.
8. Reconnect drain line union, fill valve supply line, electrical
9. Verify drain valve lever is in AUTO position.
mc_021908_1410-elec
The CRUV humidifier is again ready to humidify.
Mineral precipitate
As evaporation takes place in the humidifier, some of the minerals
dissolved in the water precipitate out and float on the water surface. The
minerals not removed by the skimmer will settle to the bottom of the
evaporating chamber.
Cleaning the evaporating chamber
The heating element is self‑cleaning. The mineral buildup on the element
flakes off after reaching a thickness of about 1/16" (2 mm), and settles to
the bottom of the chamber.
Long heater element life can be expected when the operation of the
humidifier is observed for a few weeks following initial start‑up. By
observing the mineral build‑up rate, the frequency of both drain/flush
use and manual cleaning can be determined and adjustments made.
Before this mineral scale builds up on the underside of the heating
element, it must be removed. Failure to do so could result in premature
heater burnout.
The humidifier is designed for convenient cleaning and maintenance.
Start-up
Perform the Annual safety checks in the Inspection and maintenance
section on page 4.
If resuming operation after service, do not leave the humidifier
unattended; allow it to cycle through multiple fill cycles to verify that all
serviced parts are functioning properly. See the humidifier's Installation,
Operation, and Maintenance manual for start‑up details.
(recommended).
supply line, electrical connections to drain, (disconnecting field
wiring in conduit is NOT recommended,) thermal trip, heaters,
fill valve, and probe. Disconnect steam hose from top of tank and
remove mounting bracket fasteners.
connected.
connections to drain, thermal trip, heaters, fill valve, and probe.
Connect steam hose to top of tank.
C A U T I O N
DRI-STEEM products are warranted according to the terms and conditions of the standard
two-year Limited Warranty effective when the humidifier was purchased. See the literature
that was shipped with the humidifier for warranty information.
mc_060208_1100
mc_052708_1130
mc_052908_1005
mc_081308_1405