Voltage supply of the peripheral devices

The compressor module internally supplies voltage to
peripheral devices (solenoid valves, slider position in-
dicator, oil and oil filter monitoring and/or oil heater)
and to the terminal strips CN7 to CN12.
3.3.2

Rotation direction monitoring fuse (F08)

The HS. and CS. compressors incorporating the com-
pressor module are equipped with the F08 fuse in the
terminal box. It protects the rotation direction monitor-
ing lines between terminal box and module housing.

3.4 Available cable bushings into the module housing

HS.95
OS.95
OS.85
CS.105
ST-150-4
0 .. 10 V DC, ±2% at 100% with max. 1 mA
or 4 .. 20 mA DC, ±2% at 100%, 500 Ω resistor in parallel
linear control signal required
This type of control is particularly suitable for systems with simple controllers
equipped with an output for 0 to 10 V and with a relay.
0 .. 10 V DC, linear control signal required
Modbus RTU, RS485, detailed description see BEST SOFTWARE.
recognition range: 20 .. 135 Hz at 83 .. 690 V
time delay after activation of input signal of safety chain at CN2:3: 7 s
Screwed joints:
1 x M20x1.5 for 1 cable with a clamping range between Ø 8 and 13 mm
1 x M16x1.5 for 1 cable with a clamping range between Ø 5 and 10 mm
Screwed joints:
1 x M20x1.5 for 1 cable with a clamping range between Ø 8 and 13 mm
1 x M16x1.5 for 1 cable with a clamping range between Ø 5 and 10 mm
Blind caps: 1 x M25x1.5 and 1 x M16x1.5
Screwed joints:
1 x M20x1.5 for 1 cable with a clamping range between Ø 8 and 13 mm
1 x M16x1.5 for 1 cable with a clamping range between Ø 5 and 10 mm
Blind caps: 1 x M25x1.5, 1 x M20x1.5 and 1 x M16x1.5
Cable plugs for 2 cables of Ø 7 mm
CS.105:
Screwed joint: 1 x M20x1.5 for 1 cable with a clamping range between Ø 8 and
13 mm
Blind cap: 1 x M16x1.5
Cable plugs for 2 cables of Ø 7 mm and 2 cables of Ø 5 mm
Such a fuse is also required with open compressors
between module housing and motor terminal box when
the rotation direction monitoring function of the com-
pressor module is used.
Technical data of the installed fuse:
• Rated current 1 A
• Release speed FF (very quick acting)
• Rated breaking capacity of 50 kA at 700 V AC
• Dimensions 6.3 x 32 mm