Following this, any optional extension kits can be
mounted (see chapter Mounting the optional CM-RC-01
extension kits, page 10).
3.6 Further electrical connections on the CM-RC-01
• Voltage supply of the compressor module on ter-
minal strip CN1 (115 .. 230 V +10%/-15%, 50/60 Hz
– Terminal 1: L
– Terminal 2: N
8
Mounting the opto-electronic unit
NOTICE
!
!
Risk of compressor failure!
Possible failure of the protection device
due to penetrating moisture!
Ensure that the cable connection always
faces down!
• Carefully insert the opto-electronic unit into
the prism unit up to the stop. Position and
cable routing downwards, see figure!
• Tighten the union nut of the opto-eletronic unit
by hand.
• Command for compressor start (release signal from
system controller).
• Optionally: Analogue signal for capacity control from
the system controller (0 .. 10 V).
Schematic wiring diagram and further information, see
Technical Information KT-230.
3.7 Screwing the cover onto the module housing
• Attach the enclosed adhesive label "CM-
RC-01" into the cover of the terminal box.
• Then screw the protective earth conductor to
the terminal box cover.
KW-232-1