Os.85: Monitored Functions - Bitzer CM-SW-01 Information Technique

Masquer les pouces Voir aussi pour CM-SW-01:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Monitored functions
Discharge gas temperat-
ure
Oil supply
Rotation direction (option)
Phase failure (option)
Operating recognition with
FI operation (option)
Tab. 4: State of delivery of CM-SW-01 with OS.95

7.4 OS.85: monitored functions

Monitored functions
Low pressure
High pressure
Application limits
(Condensing temperature,
evaporation temperature)
Discharge gas temperat-
ure
Oil supply
Oil filter monitoring
Rotation direction (option)
Phase failure (option)
Operating recognition with
FI operation (option)
Tab. 5: State of delivery of CM-SW-01 with OS.85
ST-150-4
Time delay
Warning
after com-
pressor start
---
> 95°C
15 s
---
3 s
---
3 s
---
7 s
---
Time delay
Warning
after com-
pressor start
---
---
---
---
120 s
< 2 K within the
application lim-
its
---
> 95°C
17 s
---
0 s
---
3 s
---
3 s
---
7 s
---
Critical alarm
Fault
---
> 100°C
CM-SW-01 switches off immedi-
ately.
---
CM-SW-01 locks out immedi-
ately.
---
CM-SW-01 locks out immedi-
ately.
---
CM-SW-01 switches off immedi-
ately.
---
CM-SW-01 locks out immedi-
ately.
Critical alarm
Fault
---
< NV
CM-SW-01 locks out immedi-
ately.
---
> PS
CM-SW-01 locks out immedi-
ately.
> 2 K outside
> 4 K outside the application lim-
the application
its
limits
CM-SW-01 switches off immedi-
CM-SW-01
ately.
locks out after
30 s.
---
> 100°C
CM-SW-01 switches off immedi-
ately.
---
CM-SW-01 locks out after 3 s.
---
CM-SW-01 issues an alarm
message.
---
CM-SW-01 locks out immedi-
ately.
---
CM-SW-01 switches off immedi-
ately.
---
CM-SW-01 locks out immedi-
ately.
57

Publicité

Table des Matières
loading

Table des Matières