2.3.1
General safety instructions
WARNING
Risk of electric shock!
Before working on the module housing and
electrical lines: Switch off the main switch and
secure it against being switched on again!
Close the module housing before switching on
again!
3 Technical data
3.1 Compressor module (K03)
Operating voltage
Required fuse (F04)
Enclosure class
Place of storage
Place of installation
EMC
Bluetooth interface
ST-150-4
115 .. 230 V +10%/-15%, 50/60 Hz, max. 600 VA
4 A quick acting at 230 V / 8 A quick acting at 115 V
Module housing in its state of delivery: IP65
Compressor module without module housing: IP20
Permitted ambient temperature: -30°C .. +80°C
Permitted ambient temperature: -30°C .. +70°C
Permitted relative humidity: 5% .. 95% (EN60721-3-3 Classes 3K3 and 3C3)
Maximum allowable altitude: 2000 m
The compressor module complies with the EU EMC directive
Interference immunity
EN61000-6-1:2007, immunity for residential, commercial and light-industrial
environments
EN61000-6-2:2005 +AC:2005, immunity for industrial environments
Emitted interference
EN61000-6-3:2007, emission for residential, commercial and light-industrial
environments
EN61000-6-4:2007 +A1:2011, emission for industrial environments
Bluetooth transmitter:
class 2, power max. 2.5 mW
range max. 10 m depending on vicinity
Approvals:
Eurofins according EN300328, EN301489-1 and EN301489-17
FCC with ID T7VPAN10
can be deactivated see chapter Deactivating the Bluetooth interface, page 60
NOTICE
!
!
The compressor module may be damaged or
fail!
Never apply any voltage to the terminals of CN7
to CN12 – not even for test purposes!
The voltage applied to the terminals of CN13
must not exceed 10 V!
The voltage applied to terminal 3 of CN14 must
not exceed 24 V! Do no apply voltage to the
other terminals!
Never apply voltage to the voltage outputs, not even for
testing.
35