General Safety Instructions; Technical Data; Compressor Module (K03) - Bitzer CM-SW-01 Information Technique

Masquer les pouces Voir aussi pour CM-SW-01:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

2.3.1

General safety instructions

WARNING
Risk of electric shock!
Before working on the module housing and
electrical lines: Switch off the main switch and
secure it against being switched on again!
Close the module housing before switching on
again!

3 Technical data

3.1 Compressor module (K03)

Operating voltage
Required fuse (F04)
Enclosure class
Place of storage
Place of installation
EMC
Bluetooth interface
ST-150-4
115 .. 230 V +10%/-15%, 50/60 Hz, max. 600 VA
4 A quick acting at 230 V / 8 A quick acting at 115 V
Module housing in its state of delivery: IP65
Compressor module without module housing: IP20
Permitted ambient temperature: -30°C .. +80°C
Permitted ambient temperature: -30°C .. +70°C
Permitted relative humidity: 5% .. 95% (EN60721-3-3 Classes 3K3 and 3C3)
Maximum allowable altitude: 2000 m
The compressor module complies with the EU EMC directive
Interference immunity
EN61000-6-1:2007, immunity for residential, commercial and light-industrial
environments
EN61000-6-2:2005 +AC:2005, immunity for industrial environments
Emitted interference
EN61000-6-3:2007, emission for residential, commercial and light-industrial
environments
EN61000-6-4:2007 +A1:2011, emission for industrial environments
Bluetooth transmitter:
class 2, power max. 2.5 mW
range max. 10 m depending on vicinity
Approvals:
Eurofins according EN300328, EN301489-1 and EN301489-17
FCC with ID T7VPAN10
can be deactivated see chapter Deactivating the Bluetooth interface, page 60
NOTICE
!
!
The compressor module may be damaged or
fail!
Never apply any voltage to the terminals of CN7
to CN12 – not even for test purposes!
The voltage applied to the terminals of CN13
must not exceed 10 V!
The voltage applied to terminal 3 of CN14 must
not exceed 24 V! Do no apply voltage to the
other terminals!
Never apply voltage to the voltage outputs, not even for
testing.
35

Publicité

Table des Matières
loading

Table des Matières