Points De Données (Requête Individuelle); Coils; Discrete Inputs - MR ECOTAP VPD MD&C Instructions De Service

Masquer les pouces Voir aussi pour ECOTAP VPD MD&C:
Table des Matières

Publicité

Address
Nom
0
Change Tap Position Raise
1
Change Tap Position Lower
1)
4
Blocking activation P5 level 1
7
F5 command inverted
10
F7.1 E1 to relay output
11
F7.2 E2 to relay output
1)
12
Blocking activation P5 level 2
Tableau 15: Coils
Address
Name
0
E1 No connection to EXTERNAL CONTROL
1
E2 EXTERNAL CONTROL command could not be
performed.
2
E3.1 Error in connection between control unit and
motor-drive unit
3
E3.2 Error in connection between control unit and
motor-drive unit
4
E3.3 Error in connection between control unit and
motor-drive unit
5
E3.4 Error in connection between control unit and
motor-drive unit
6
E4.1 Automatic adjustment not undertaken or incor-
rect.
7
E4.2 The desired target position could not be rea-
ched when voltage failed.
8
E5.1 System not ready
9
E5.2 System not ready
10
E5.3 System not ready
11
E6.1 Tap change command cannot be performed
12
E6.2 Tap change command cannot be performed
®
®
92
ECOTAP
VPD
MD&C
8.4 Points de données (requête individuelle)

8.4.1 Coils

1) P5 inactif lorsque « coil 4 » = 0 et « coil 12 » = 0

8.4.2 Discrete Inputs

8 Protocole poste de conduite (en option)
Coil Status
1 = raise
1 = lower
1 = active (level 1)
1 = active
1 = active
1 = active
1 = active (level 2)
Coil status
1 = active
1 = active
1 = active
1 = active
1 = active
1 = active
1 = active
1 = active
1 = active
1 = active
1 = active
1 = active
1 = active
6117331/03 FR
EXTERNAL CONTROL
R = read / W = write
CONTROL PRO
R/W
R/W
R
R
R
R
R
EXTERNAL CONTROL
R = read/W = write
CONTROL PRO
R
R
R
R
R
R
R
R
R
R
R
R
R
Maschinenfabrik Reinhausen GmbH 2020
Others
R/W
R/W
R
R/W
R/W
R/W
R
Others
R
R
R
R
R
R
R
R
R
R
R
R
R