DRIVE WIRING, CONT'D
For Analog Pressure Transducer
NOTE: A 10 ft (3 m) section of pressure transducer cable is provided with the analog pressure transducer kits.
Other lengths are available. See the "Accessories" section on page 26 for ordering information.
a. Locate the terminal block labeled TRANSDUCER (XDCR).
b. Connect the RED lead of the pressure transducer cable to the "+" terminal of the XDCR terminal block.
c. Connect the BLACK lead of the pressure transducer cable to the "-" terminal.
d. Connect the bare shield lead of the pressure transducer cable to the S terminal (where applicable).
e. Tighten terminals to 5 in-lbs (0.6 Nm) with a small screwdriver (provided).
f.
Plug the other end of the transducer cable into the pressure transducer.
9. Verify that the SubDrive Utility unit is properly configured for the horsepower rating of the motor and pump being used
(see the "Drive Configuration" section on page 21).
10. Verify that the SubDrive Utility is correctly configured for the pressure sensor type being used.
11. Replace the cover. Tighten screw to 10 in-lbs (1.1 Nm).
12. Set the pressure tank pre-charge at 70% of the desired water pressure setting. To check the tank's pre-charge,
depressurize the water system by opening a tap with the drive off (see Table 3 on page 16).
Measure the tank pre-charge with a pressure gauge at its inflation valve and make the necessary adjustments.
20