SMA INVERTER MANAGER Instructions D'installation page 34

Masquer les pouces Voir aussi pour INVERTER MANAGER:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

5  LCS-Tool
Figure 24: LCS-Tool - Overview of current system values
Modbus control
To make this limitation permanent, set the desired
value in the Modbus register 40349.
To disconnect the inverter immediately from the utility
grid while the Limited Export function is running, set
the value "0" in the Modbus register 40348.
For further information on the Modbus interface see
technical information "SUNNY TRIPOWER 60 /
SUNNY HIGHPOWER PEAK1 - SunSpec®
Modbus® Interface" at www.SMA-Solar.com.
Figure 25: Feeding-in operation with Limited Export / Peak Load Shaving
34
IMVIOBOX-IA-xx-19
SMA Solar Technology AG
Installation Manual

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Digital i/o boxLcs-tool

Table des Matières