4.3

Operating structure

4.3.1

General notes on operating

- All configuration data, measurement and controller parameter can be accessed
(↑-key from the measuring mask) from the main menu.
- The last line in the respective setting menu shows the keys that effect the respective cursor
position.
- Every set value can be changed directly at its position in the setting menu. The cursor must
be positioned on the corresponding selection and can then be moved to the set value with
the →-key. The ↑ and ↓ keys are used to set one value from between specific limits. The
value is changed by one digit through operating one of the two keys once. The value
changes continuously if the key is operated for a longer period; the value at which point the
corresponding arrow key is released is the one that remains. The value is adopted through
operating the ENTER key. The ←-key is used to cancel the respective setting.
- If set values have changed, these are saved during the change to the operating level
(measurement mask). Only the changed values are adopted.
CAUTION

4.3.1.1 Operating diagram

Fig. 4.3
417101163_Multronic.doc
All the controllers are turned off when adjusting the values in the configuration menu, i.e.
fast processes can result in significant set point deviations during the adjustment phase.
The effects of significant set point deviations must therefore be determined in advance and
suitable counter measures should be implemented if required.
The same applies when operating the device using "manual functions". Here too all control
system functions are switched off. The effects of manually operated pumps, valves etc. on
the process must be taken into account whatever the circumstances.
- 50 -
Rev: 5.07-08