cegard/Lift LX/LY
9.
Error diagnosis
9.1.
Plug-in system controller, interface for
elevator control
The 7-segment display on the plug-in system con-
troller is used as an error, status and diagnosis dis-
play. The numbers 0-9 serve as error indications.
Each number is allocated to a possible error.
The 7-segment display flashes with the respective
error number if an error occurs.
Internal error on plug-in system controller:
Switch off unit, check wiring
-
Activate unit
-
Please contact your nearest CEDES
-
office if the error occurs again
Power-up (static display), control unit
plug-in_1 not enabling.
Please check your strip installation
-
Is the monitored area free?
-
See section 9.2
-
Operating (flashing display):
The connection between the plug-in
-
system controller and control unit
plug-in_1 is interrupted or the control
unit plug-in is defective.
Check cables and plugs
-
See section 9.2
-
Same as error #1, but for control unit
plug-in_2.
Wrong software version. Plug-in system
controller is designed for two entrances,
but the software is only for one entrance.
Please contact a CEDES office.
Not used.
The override delay signal is permanently
low.
Check the signal wiring (the input
-
should be closed)
The signal should carry out a clear
-
signal change (low-high) at least once
per journey.
Additionally check voltage level.
-
See section 3.2.3
-
The Option2 signal is permanently low.
Same procedure as with error #5, but in-
volving the Option2 input.
24
Installation and Operation Manual
The safety circuit, the safety check circuit
or an external contactor is either perma-
nently broken or closed.
The latch relay, the latch check circuit or
an external latch contactor is either per-
manently open or closed.
Not used
Ensure that the Override delay (Überbrückungs-
verzögerung) control signal and Option 2 can,
under no circumstances, assume an improper
status. This is particularly important while travelling
during inspection or commissioning , as errors 5
or 6 will occur.
9.2.
Control unit plug-in with optical strips
The LED displays on the control unit plug-in are
used for light curtain component diagnosis and error
location.
The following are possible causes of error if error 1 or 2
occur on the plug-in system controller:
1. "Power" LED on
control unit plug-in
does not illuminate!
2.The buzzer sounds
constantly when light
beam is free!
3.How can a light curtain
component error be
localized?
www.cedes.com
Please check correct connection
-
See sections 5 & 6
-
Please check correct connection
-
See section 5 & 6
-
Check the control unit plug-in supply
voltage (17 ... 30 VDC via terminal
"GND" and "V+"). Check the SI1 fuse
on the control unit plug-in.
Is the light beam free across the entire
plane? Are all sensor elements free?
A gap of at least 7 mm should be free.
The following errors can be located
after activation by monitoring the
LEDs "Alarm R" and "Alarm T" (see
table "Control unit plug-in error diag-
nosis"):
© CEDES/October 2008