6.2.6
LA: Language
Display in one of the following languages:
Italian
English
French
German
Spanish
Dutch
Swedish
Turkish
Slovenian
Romanian
6.2.7
HO: Operating hours
Indicates, on two lines, the hours of inverter activation and pump operating hours.
6.3 Setpoint menu
From the main menu, press and hold MODE and SET simultaneously until "SP" appears on display (or use
the buttons + or – in the selection menu).
Buttons + and – enable respectively to increase and decrease the system pressurisation value.
To exit the current menu and return to the main menu, press SET.
This menu enables the user to set the system operating pressure.
The pressure range depends on the sensor used (see PR: Pressure sensor section 6.5.7) and varies as
shown in Table 15. System pressure can be displayed in [bar] or [psi] depending on measurement system
used.
Type of sensor used
16 bar
25 bar
40 bar
Table 15: Maximum regulation pressure values
6.3.1
SP: Setting the setpoint pressure
Pressure to apply to the system if the auxiliary pressure regulation functions are not active.
6.3.2
P1: Auxiliary pressure 1 setting
Pressure to apply to the system if the auxiliary pressure function is activated on input 1.
6.3.3
P2: Auxiliary pressure 2 setting
Pressure to apply to the system if the auxiliary pressure function is activated on input 2.
ENGLISH
Regulation pressure values
Regulation pressure [bar]
1,0 - 15,2
1,0 - 23,7
1,0 - 38,0
87
Regulation pressure [psi]
14 - 220
14 - 344
14 - 551