NOTE
It is mandatory to use both lifting
points (2) set up on the roof from the
control side and on the opposite
side. The brackets set up on the
lifting points are provided with 3
holes used to find the centre of
gravity. The lifting hook must be
positioned as close to the centre of
the
generator's
possible to keep it from swaying
when lifted. The length of the 2
lifting chains (1) must form an angle
of approximately 40° between the 2
chains: this limits the stress on the
lifting elements.
STANDARD SOUNDPROOF: 4 lifting points
Detail of the position of the lifting points below:
74
4.INSTALLATION
lifting
points
as
NOTE
It is mandatory to use all 4 lifting
points (2) set up on the roof: 2 from
the controls side and the other 2 on
the opposite side. The main lifting
hook (3) must be positioned as close
to the centre of the generator's four
lifting points as possible to keep it
from
swaying
necessary, adjust the length of the
lifting chains to balance the load. The
length of the 4 lifting chains (1) must
form an angle of approximately 40°
between the 2 chains: this limits the
stress on the lifting elements.
SOUNDPROOF with "EFT" (Extended Fuel
Tank): 4 lifting points
GSW
when
lifted.
If