7.TROUBLESHOOTING
Speed is too low.
The relative instruments are faulty.
Instrument connections.
The switch has tripped due to
overvoltage.
Power surge.
●
●
The main switch has been activated.
Short-circuit or faulty earthing.
Faulty auxiliary services.
No power supply.
●
The oil level is high.
The oil level is low.
Blocked oil filter.
Faulty oil pump.
The coolant level in the radiator is
low.
Faulty water pump.
A malfunction in the relative alarm:
the sensor, electric control panel or
electric connections are faulty
●
●
●
Possible cause
Check the speed regulator if the
engine is equipped with it. If the
engine is not equipped with a
mechanical speed regulator, contact
the after-sales assistance centre to
request assistance.
Check and replace if necessary.
Check
instruments.
Reduce the overvoltage.
Check that the generator is not in
overload conditions, even in relation
to the ambient temperature which
could be higher than normal.
Check all the circuits in relation to
any type of machine damage or
connection cables.
Contact the after-sales assistance
centre to request assistance.
Check the power circuits.
Remove excess oil.
Add oil to restore the oil level in the
engine block. Check that there is no
leakage.
Replace the filter.
Contact the after-sales assistance
centre to request assistance.
Wait for the machine to cool off and
check the liquid level in the radiator;
add coolant if necessary. Check that
there is no leakage.
Contact the after-sales assistance
centre to request assistance.
Check
between the sensor and the panel.
Verify that the electric connections
of the sensor are not earthed. Check
the
necessary.
GSW
Solution
the
connections
of
the
the
electric
connections
sensor
and
replace
it
if