Ser
Serial communications
Unit identification code for serial
(ode
communication (if enabled)
[see "hrd.1" in Hrd]
38
Serial interface
ser. p
protocol CENCAL,
MODBUS
39
InP
Input settings
sp. t y
Setpoint type: LOC/REM,
Select type of remote
setpoint
[0...3]
44
type
Probe type, signal, enable custom linearization,
45
PROBE:TC (SEnS=0)
tYPE Probe type
0
J (Fe-CuNi)
1
J (Fe-CuNi)
2
K (NiCr-Ni)
3
K (NiCr-Ni)
4
R (Pt13Rh - Pt)
5
R (Pt13Rh - Pt)
6
S (Pt10Rh - Pt)
7
S (Pt10Rh - Pt)
8
T (Cu-CuNi)
9
T (Cu-CuNi)
10
B (Pt30Rh - Pt6Rh)
11
B (Pt30Rh - Pt6Rh)
12
E (NiCr-CuNi)
13
E (NiCr-CuNi)
14
N (NiCrSi-NiSi)
15
N (NiCrSi-NiSi)
16
(Ni - Ni18Mo)
17
(Ni - Ni18Mo)
18
L - GOST (NiCr-CuNi)
19
L - GOST (NiCr-CuNi)
20
TC
21
TC
PROBE: RTD 3 wires (SEnS=1)
tYPE Probe type
0
PT100
1
PT100
2
JPT100 (JIS C 1609/81)
3
JPT100 (JIS C 1609/81)
4
RTD
5
RTD
PROBE: PTC (SEnS=2)
tYPE Probe type
0
PTC 990Ω
1
PTC 990Ω
2
PTC 990Ω
3
PTC 990Ω
PROBE: VOLTAGE 50mV (SEnS=3)
tYPE Signal type
0
0...50mV
1
0...50mV
2
10...50mV
3
10...50mV
0 ... 9999
SEr.P Serial protocol
0
CENCAL GEFRAN
1
MODBUS RTU
SP.tY
Type of remote
setpoint
0
analogue (InP.2)
1
analogue (InP.2)
2
digital
(from serial line)
3
digital
(from serial line)
+4 set gradient in digit / sec
and main input scale
Scale
Scale range max.
(C/F)
without decimal point
C
0 / 1000
F
32 / 1832
C
0 / 1300
F
32 / 2372
C
0 / 1750
F
32 / 3182
C
0 / 1750
F
32 / 3182
C
-200 / 400
F
-328 / 752
C
44 / 1800
F
111 / 3272
C
-100 / 750
F
-148 / 1382
C
0 / 1300
F
32 / 2372
C
0 / 1100
F
32 / 2012
C
0 / 600
F
32 / 1112
C
custom scale
F
custom scale
Scale
Scale range max.
(C/F)
without decimal point
C
-200 / 850
F
-328 / 1562
C
-200 / 600
F
-328 / 1112
C
custom scale
F
custom scale
on request, instead of RTD 3 wires
Scale
Scale range max.
Scale range max.
(C/F)
without decimal point
with decimal point
C
-55 ... 120
-55.0 ... 120.0
F
-67 ... 248
-67.0 ... 248.0
C
custom scale
F
custom scale
Scale
Scale range max.
linear
-1999 / 9999
custom linear
see table 32 values in Lin
linear
-1999 / 9999
custom linear
see table 32 values in Lin
• Ser
bavd
40
par
-
101
• InP
Absolute
Relative
absolute
relative to
local setpoint
absolute
relative to
local setpoint
Scale range max.
PROBE: CURRENT 20mA or TRANSMITTER (SEnS=4)
with decimal point
0.0 / 999.9
tYPE Signal type
32.0 / 999.9
0
0...20mA
0.0 / 999.9
1
0...20mA
32.0 / 999.9
2
4...20mA
not available
3
4...20mA
not available
not available
PROBE: VOLTAGE 10V or TRANSMITTER (SEnS=5)
not available
tYPE Signal type
-199.9 / 400.0
0
0...10V
-199.9 / 752.0
1
0...10V
not available
2
2...10V
not available
3
2...10V
-100.0 / 750.0
-148.0 / 999.9
PROBE: CUSTOM 10V (SEnS=6)
0.0 / 999.9
32.0 / 999.9
tYPE
0.0 / 999.9
0
32.0 / 999.9
0.0 / 600.0
1
32.0 / 999.9
(*)
(*)
PROBE: CUSTOM 50mV, 20mA (SEnS=7)
tYPE
0
Scale range max.
1
with decimal point
-199.9 / 850.0
-199.9 / 999.9
-199.9 / 600.0
(*) Linearization and scale limit settings (with or without decimal point) are
-199.9 / 999.9
selectable from PC via serial line
(*)
(*)
(*)
(*)
22
Select Baudrate
bAud Baudrate
CENCAL Interface
0
1200
CL / 485 / 232
1
2400
485 / 232
2
4800
485 / 232
3
9600
485 / 232
4
19200
485 / 232
PAr
Parity selection
Scale
Scale range max.
linear
-1999 / 9999
custom linear
see table 32 values in Lin
linear
-1999 / 9999
lineare custom
see table 32 values in Lin
Scale
Scale range max.
linear
-1999 / 9999
custom linear
see table 32 values in Lin
linear
-1999 / 9999
custom linear
see table 32 values in Lin
Signal type
Scale
Custom 0...10V
linear
Custom 0...10V
custom linear
Signal type
Scale
Custom
lineare
Custom
custom linear
MODBUS Interface
485
485
485
485
485
Parity
0
No parity
1
Odd
2
Even
Scale range max.
-1999 / 9999
see table 32 values
in Lin
Scale range max.
-1999 / 9999
see table 32 values
in Lin