Function indicators
Indicates modes of operation
MAN = OFF (Automatic control)
MAN = ON (Manual control)
AUX = OFF (IN1 = OFF - local Setpoint 1)
AUX = ON (IN1 = ON - local Setpoint 2)
REM = OFF (local Setpoint)
REM = ON (remote Setpoint)
"Raise" and "Lower" key
Press to increment (decrement) any numerical
parameter ••
Increment (decrement) speed is proportional to time
key stays pressed ••
The operation is not cyclic: once the maximum
(minimum) value of a field is reached, the value will
not change even if the key remains pressed.
• Power Supply
Standard:
100...240Vac/Vdc ±10%
~
12
Optional:
PWR
20...27Vac/Vdc ±10%
~
13
50/60Hz, 12VA
• Outputs
User configurable generic
(-) NC
14
- 5A/250Vac relay, cosϕ=1
C
15
- 11Vdc logic, Rout=220Ω
(6V/20mA)
(+) NO
16
(-) NC
17
C
18
(+) NO
19
(-) NC
20
C
21
(+) NO
22
• Serial line
Configurable serial
27
-
line isolated to 1500V
Tx
Passive current loop
26
+
(max. 1200 baud)
25
-
RS422/485 or RS232
Rx
(optional)
24
+
• Linear (V)
Linear input in dc voltage
2
0...50mV, 10...50mV,
0...10V, 2...10V
1
3 • DESCRIPTION OF FACEPLATE
4 • CONNECTIONS
output
!
12
13
14
15
16
17
18
19
20
21
22
A +
Tx
B -
1800
GND
Rx
RS485 2-wires
RS232
• Linear (I)
Linear input in dc
current
-
0...20mA, 4...20mA
+
User configurable
33
+W2
generic output
- analogue output
32
+W1
isolated to 1500V
(0 ... 10V, 0 ... 20mA,
4 ... 20mA)
31
0V
33
11
32
10
31
9
30
8
29
7
28
6
27
5
26
4
25
3
24
2
1
1600
• Pt100 2 wires o PTC
Use wires of adequate
4
diameter (min. 1mm
PT100, JPT100, PTC
2
-
1
+
19
Indication of output states
OUT 1 (Open); OUT 2 (Close);
OUT 3 (AL 1); OUT 4 (HB)
PV Display: Indication of process variable
Error Indication: LO, HI, Sbr, Err
LO= the value of process variable is < di LO_S
HI= the value of process variable is > di HI_S
Sbr= faulty sensor or input values higher than max.
limits
Err= PT100 third wire opened for PT100, PTC or
input values lower than min. limits
(i.e.: TC wrong connection)
SV display: Indication of setpoint
Function key
Gives access to the various configuration phases ••
Confirms change of set parameters and browses
next or previous parameter (if Auto/Man key is
pressed)
Automatic/Manual adjustment selection
Active only when PV display visualises the process
variable
• Outputs
User configurable
generic output
- 5A/250Vac relay, cosϕ=1
- 11Vdc logic,
Rout=220Ω (6V/20mA)
• Transmitter supply
Transmitter supply isolated
1500V
10/24Vdc, max. 30mA
short-circuit protection
• Digital inputs
Digital inputs isolated
1500V
- NPN 24V, 4,5mA
- PNP 24V, 3,6mA
(12V, 1,2mA)
• Auxiliary input
Auxiliary input isolated
9
1500V
Current transformer
50mAac; 1,5Ω; 50/60Hz
6
Remote setpoint
0...20mA, 4...20mA, 5Ω,
0...1V, 0...10V,> 1MΩ
5
Potentiometer > 500Ω
• Inputs
Available thermocouples:
J, K, R, S, T, B, E, N,
Ni-Ni18Mo, L NiCr-CuNi
- Observe polarities
- For extensions, use the
correct compensating
cable for the type of TC
used
3
2
)
2
T
1
11
-
Out4
(AL2 / HB)
10
+
9
+ Vt
5
GND
8
IN2
7
IN1
5
COM
+Vt
+10V
~
+
Pot
GND
-
~
• TC
-
2
1
+
• Pt100 3 wires
3
2
T
1