Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

English
Reference
Speed potentiometer across 1(low),
9(high), 2(wiper) OR
External 2-wire speed reference between
1(-) and 2(+)

Speed Feedback

The Speed Feedback Card is required only for closed
loop Flux Vector Control
Static Sensitive Board. Install only with
power OFF and follow proper
static/grounding procedures
Install it on the feedback header, shown by the red arrow
in the figure. Ensure a good fit by securely snapping in
place.
DIP switches 1,2,3,4 (blue arrow) set the threshold voltage
of the encoder signals. Set all switches to ON (up position)
for complementary encoder signals.
Encoder connections to terminal block are:
1 Encoder Supply positive (5–15VDC)
2 Encoder Supply negative (0V)
3 Channel A
4 Channel A complement
5 Channel B
6 Channel B complement
CAUTION
Sequencing
Jumper 19 and 20 if no external trip contact
Start contact between 12 and 20
Jog contact between 16 and 20
Reverse Direction contact between 15 and 20
Health volt-free contacts between 21 and 22
Running volt-free contacts between 23 and 24
1-4

Publicité

Table des Matières
loading

Table des Matières