Normal Operation - Burkert 3005 Mode D'emploi

Masquer les pouces Voir aussi pour 3005:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

learning mode
specify end positions
8.3.3.
normal operation
Display normal operation
32
Press <OPEN> and <CLOSE> push-buttons and switch on the card
(hold down push-button).
The RED and the GREEN LEDs light up.
G
R
Release <OPEN> and <CLOSE> push-buttons.
Both LEDs go out.
Learning mode is selected.
Press <CLOSE> push-button to move the shut-off valve into the
closed position.
R
The RED LED lights up.
Press <MEM> and <CLOSE> push-buttons to save the closed
position.
R
The RED LED lights up 2x.
Press <OPEN> push-button to move the shut-off valve into the open
position.
G
The GREEN LED lights up.
Press <MEM> and <OPEN> push-buttons to save the open position.
R
The GREEN LED lights up 2x.
All positions are now saved.
Disconnect the card from the power supply.
Switch on card.
The GREEN LED lights up 3x to indicate that the start process has been
G
implemented correctly.
In normal operation the GREEN LED lights up when the rotary actuator
G
opens the shut-off valve.
The RED LED lights up when the rotary actuator closes the shut-off valve.
R
If neither of the LEDs is lit, the actuator is not actuated.
G
R
The RED and the GREEN LEDs light up if the torque is too high and the
rotary actuator stops.
G
R
Change direction of rotation of the rotary actuator or switch over the
voltage OPEN/CLOSED to restart the rotary actuator!
English
Type 3005
Installation

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Type 3005

Table des Matières