MDR .. EC
● Factory settings: 50 % of the selected measur-
ing range 75 Pa
Parameter pressure control range
● Low value = fast regulation
● High value = slow regulation (high stability)
● Setting range: in the measuring range of the
sensor
● Factory settings: 50 % of the selected measur-
ing range 200 Pa
Parameter 0.0 V Min. V out
Minimum output voltage
● Setting range: 0...10 V (priority over
"Max. V out")
● Factory settings: 0 V
Parameter 10.0 V Max. V out
Maximum output voltage
● Setting range: 10...0 V
● Factory settings: 10 V