3. The display changes to the actual value
display and after the zero point has been
calibrated, the value "0" is displayed.
4. The required difference up to "0" is dis-
played in the BASE SETUP under "Offset".
Setting 0 Pa/offset
As an alternative to the automatic zero point
adjustment, the offset value can also be set
manually (setting range ± 1000 Pa).
Parameter OFF/factory setting
ON = Reset to factory settings
(= delivery status).
Settings for operation (SETTING)
Parameter setpoint 1 (setpoint 1)
● Setting range: In the measuring range of the
sensor
● Factory settings: 50 % of the selected measur-
ing range 100 Pa
Parameter setpoint 2 (setpoint 2)
● Setting range: In the measuring range of the
sensor