Menu no.
Display
visible for
User 1 and higher:
Calling up
User 2 and higher:
by:
Service:
4.3.5.1
FC parameters (page 1of2)
FC
parameters
CC-FC
FC parameters (page 2of2)
4.3.5.1
FC parameters (page 1of2)
FC
parameters
CCe
FC parameters (page 2of2)
4.3.5.2
FC status (Page 1of2)
FC status
CC-FC
FC status (Page 2of2)
Installation and operating instructions Wilo-Control CC-Booster
Description
*
**
***
*
Setting of the maximum and mini-
mum output frequency and ramp
times of the frequency converter,
specification of the frequency con-
verter type (the drives have to be
switched off for this)
Setting of FC frequencies to avoid
*
controlled variable leaps during
peak-load switching on and off
Setting of FC frequency with which
the controlled pump should run dur-
ing sensor fail
*
Setting of the maximum and mini-
mum output frequency and ramp
times of the frequency converter,
specification of the frequency con-
verter type (the drives have to be
switched off for this)
*
Setting of the voltage range for the
analogue outputs for the e-pumps
Setting of the FC frequency with
which the controlled pump should
run during sensor fail
*
Display of status signals of the bus
connection and frequency converter
*
Display of warning signals from the
frequency converter
(Voltage, current, temperature)
Setting parameters/
Factory setting
functions
adjustable by
User 1 and higher:
*
User 2 and higher:
**
Service:
***
f
[Hz]
**
25...50...60
max
**
f
[Hz]
20...35...50
min
t
+ [s]
1...5...60
Ramp
**
t
- [s]
1...5...60
**
Ramp
FU type
FC202 /
*
VLT2800 /
VLT6000
f
+ [Hz]
20.5...50...60
**
Peak filter
**
f
- [Hz]
20.5...35...60
Peak filter
f
[Hz]
20.5...40...60
**
Sensor error
U
[V]
**
0...2...4
max
**
U
[V]
8.0...10.0
min
**
t
+ [s]
0.0...60
Ramp
**
t
- [s]
0.0...60
Ramp
f
[Hz]
**
0.0...80.0...100.0
Sensor error
None
-
None
-
English