Wilo W-CTRL-CC Série Notice De Montage Et De Mise En Service page 63

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Menu no.
Display
visible for
User 1 and higher:
Calling up
User 2 and higher:
by:
Service:
4.3.3.2
Peak-load pump, general
CCe
4.3.3.3
PID controller
PID controller
4.3.3.4
Manual control mode
Manual
control
mode
CCe
CC-FC
4.3.3.5
Zero-flow test
Zero-flow test
CCe
CC-FC
4.3.3.6
Pipe fill function
Pipe fill
function
4.3.4
Pump parameters
Pump
parameters
4.3.4.1
Number of pumps
Number of
pumps
Installation and operating instructions Wilo-Control CC-Booster
Description
*
**
***
*
Display/setting of start-up and
switch-off pressure, as well as start-
up and switch-off delay of peak-load
pump (entry of all values in % of 1st
setpoint of controlled variable.)
Setting of proportional value, reset
*
time, preset time
*
Settings for operation of pumps by
means of external analogue value.
The setting range of the analogue
signal and the operation with one
pump or all pumps (only CCe) can be
selected.
*
Parameter for the zero-flow test for
deactivating the base-load pump
*
Activation of pipe fill function for
controlled filling of pipes during
commissioning and system restart
*
Call-up of menu for setting the num-
ber of pumps, the parameters for
pump cycling or the pump test run,
and the pump operating mode
(only CCe)
*
Setting of the number of pumps of
the system (1...6) and specification of
operation with/without standby
pump
Setting parameters/
Factory setting
functions
adjustable by
User 1 and higher:
*
User 2 and higher:
**
Service:
***
Start [%]
**
75...90...100
Stop [%]
100...105...125
**
T-on [s]
0.1...3...60
**
T-off [s]
0.1...0.5...60
**
KP:
0.0...25.0...999.9
**
TI [s]
0.0...5.0...999.9
**
TD [s]
0.0...1.0...999.9
**
AutoPID
*
Manual control mode
**
on / off
Signal type
0..20mA /
**
4...20mA
**
Single/multi-pump
E/M
operation
Delay time [min]
**
1...3
Setpoint increase [bar]
0.1...0.3...1.0
**
Bandwidth [bar]
**
0.1...0.2...0.5
Duration [s]
**
1...180
Pipe fill function
**
on / off
Duration [s]
0...10...60
**
Switch-on level [%]
0.0...50.0...99.9
**
None
-
Number of pumps
**
1...3...6
Standby pump
with / without
**
English
57