Controller parameter (page 1 of 2)
Controller
parameter
Controller parameter (page 2 of 2)
4.3.3.1
Base-load pump
Base-load
pump
CC-FC
4.3.3.1
Base-load pump
Base-load
pump
CCe
CC
4.3.3.2
Peak-load pump, general
Peak-load
pump
CC
CC-FC
4.3.3.2
Peak-load pump, specific
CC
CC-FC
56
Description
*
**
***
*
Call-up of menu for setting the con-
troller parameter of the basic load
switch, the peak load switch, the PID
controller, as well as for manual con-
trol mode
*
Call-up of menu for setting the
parameters for the zero-flow test,
the pipe fill function, and for the suc-
tion mode
Zero-flow test only visible for CC-FC
and CCe
*
Display/setting of start-up and
switch-off pressure, as well as start-
up and switch-off delay of base-load
pump
(Entry of all values in % of 1st set-
point of controlled variable.)
Stop without FU only visible for
CC-FC and CCe
*
Display/setting of start-up and
switch-off pressure, as well as start-
up and switch-off delay of base-load
pump
(Entry of all values in % of 1st set-
point of controlled variable.)
Display/setting of start-up and
*
switch-off pressure, as well as start-
up and switch-off delay of peak-load
pump (entry of all values in % of 1st
setpoint of controlled variable.)
Selection possibility:
equal deactivation pressure of all
peak-load pumps
switch-off pressure specific to each
peak-load pump
*
Display/setting of specific switch-off
pressures of peak-load pumps (entry
in % of 1st setpoint of controlled
variable.)
Setting parameters/
Factory setting
functions
adjustable by
User 1 and higher:
*
User 2 and higher:
**
Service:
***
None
-
Suction mode
*
ON / OFF
Start [%]
**
75...90...100
Stop [%]
100...105...125
**
Stop without FU [%]
100...110...125
**
T-off [s]
1...10...60
**
Start [%]
**
75...90...100
Stop [%]
100...110...125
**
T-off [s]
1...10...60
**
Start [%]
75...90...100
**
Stop [%]
100...110...125
**
T-on [s]
1...3...60
**
T-off [s]
1...3...60
**
Stop 1 ... 5 [%]
**
System
dependent