5.4 Accessories
Accessories must be ordered separately:
Option
Signal module
DDC and control module
GSM module
GPRS module
WebServer
Communication module "Profibus DP"
Communication module CanOpen
Communication module "LON"
Communication module "ModBus RTU"
"BACnet" communication module
PTC relay
Signal converter U/I
Switch cabinet air-conditioning
Switch cabinet lighting
Plug
Soft starter
Energy measurement
Battery-backed power supply unit
Mains switching
Redundant pressure measurement
Pre-pressure measurement
Level relay
Overvoltage protection
Phase monitoring
Application-specific housing design
Master slave operation
Redundant FU
Redundant control
Valve control
6 Description and function
6.1 Description of the product (Fig. 1)
6.1.1 Function description
The Comfort control system, controlled by a pro-
grammable logic controller (PLC), is used to con-
trol and regulate pressure boosting systems with
up to 6 individual pumps. The pressure of a system
is controlled as a function of the load with appro-
priate signal transmitters. The controller acts on
a frequency converter (CC-FC design), which in
turn influences the speed of the base-load pump.
A modification of the speed changes the volume
flow and thus the power output of the pressure
boosting system.
40
Description
Relay output module for issuing individual operating and fault
signals
Input terminal assembly for switching potential-free control
contacts
GSM module for dialling into GSM networks
Mobile radio module for dialling into GPRS networks
Controller module for connection to Internet or Ethernet data
transmission
Bus communication module for "Profibus DP" networks
Bus communication module for "CanOpen" networks
Bus communication module for "LON" networks
Bus communication module for "ModBus" networks
Bus communication module for "BACnet" networks
Analysis relay for connecting PTC resistors (motor monitoring)
Converter for connecting voltage signals (0/2-10V)
as actuator input
Cooling/heating of switch cabinet
Interior lighting of switch cabinet
Plug in switch cabinet (fused)
Soft starter of pumps
Module to register electrical parameters
(e.g. energy consumption) of the control device
Continued power supply to PLC in the event of a mains outage
Assembly for switching to redundant supply network
2nd Pressure sensor + 2nd Analogue input in case of a fault
Measurement/display of the system's pre-pressure
Relay for evaluation of water-shortage electrodes
Equipment for protecting the device and the sensors against
overvoltage
Phase relay and/or phase lights
Material; type of protection; vandalism security; installation
site
2 devices in master/slave mode
Only the base-load pump is controlled by speed.
Non-regulated peak-load pumps are switched on
and off automatically according to load require-
ments, while the base-load pump handles fine-
tuning to the preset setpoint.
In the CCe version, each pump has an (integrated)
frequency converter.