CONDENSATE DRAIN CONNECTIONS

During functioning in cooling mode the internal
unit removes humidity from the air. The
condensate water must be eliminated by linking
the proper drainage pipe attachment with the
condensate system drain pipe.
In the "Module 600" unit, the polystyrene basin
has a hole that allows to empty the condensate,
useful in the case of disassembly.
The draining hole must always be closed again
using the rubber cap.
The units are supplied as standard with a number
of floating pump-floats for lifting the condensate
from the basin to the drainage consisting of one
electric card, one electric pump with non-return
valve and float with three-level sensors: ON, OFF
and Alarm.
CONNECTIONS FOR THE INTAKE OF EXTERNAL FRESH AIR
The unit can be connected to a fresh air intake
duct through the circular flange accessory,
applied to the vent. The application of the
CONNECTION FOR THE AIR FLOW CONDITIONED IN AN ADJOINING ROOM
The unit can be connected to a pipe for
conditioned air flow into an adjacent

ELECTRIC CONNECTIONS

The unit must be connected directly to an
electrical outlet or to an independent
circuit.
The FCL cassette fan coils must be powered
with 230V ~ 50Hz current and have an
earth connection. The line voltage must
remain within the tolerance of ±10% with
respect to the nominal value.
In order to protect the unit against short
circuits, mount a max. 2A 250V (IG)
magnet circuit breaker omnipolar switch
GLL10
GLF10
GLL20
GLL10M
GLF10M
GLL20M
GLL10R
GLF10EH
GLL20R
30
IFCLIJ 1805 - 4528500_09
The electrical supply to the pump-float device
must never be interrupted.
In the case of alarm the lifting device, interrupts
the flow of water in the coil.
The basin is fitted with an overflow hole to ensure
that the condensate water runs off if the pump-
float device is not working. In this case dripping
can be seen from the grid.
The pump allows a maximum head of 80 cm
from the level of the suspended ceiling. If this
height is not sufficient an aux. device must be
used.
It is advised to use heat-insulated rigid piping
in order to avoid condensation on the outer
surfaces.
flange requires the opening of a hole on the
side. Connection to the outside is direct and
independent from unit ventilation.
room, via the circular flange. The
application of the flange requires the
on the power supply line with a minimum
contact opening distance of 3 mm.
The electrical power supply cable must
be of the H07 V-K or N07 V-K type with
450/750V insulation if inside a tube
or raceway. Use cables with double
H5VV-F type insulation for visible cable
installation.
Refer to the wiring diagrams of the
appliance and the control panel.
A-1
A
C
1
1
1
N
SC1 = Condensate drain (male Ø 16mm)
SC2 =Condensate drain with syphon (male Ø
16mm). Ensuring a vertical section of at least 5 cm
(from the pump outlet, upward)
1
2
The accessory also includes a deflector to be
mounted inside the unit.
opening of a hole on the side.
230VAC
B-1
B
D
230VAC
L
2
2
N
2
230VAC
1/50 ~ 1/100
230VAC

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Fcl 36Fcl 42Fcl 62Fcl 72Fcl 34Fcl 38 ... Afficher tout

Table des Matières