Electrical Connections - AERMEC TS 13 Manuel D'utilisation Et D'installation

Ventilo-convecteur à pression
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

BRACKET ASSEMBLY
ELECTRIC CONNECTIONS
FEATURES OF THE CONNECTION
CABLES
Use H05V-K or N07V-K type cables
with 300/500 V insulation enclosed in a
pipe or duct.
Minimum thickness of the line cable:
1.5mm.
All cables must be enclosed in a pipe
or duct until they are inside the air han-
dling unit.
The cables exiting the pipe or duct must
be positioned in a way so that they do
not undergo pulling or twisting and are
protected against external agents.
Wire strand cables can only be used
Omnipolar magnet-circuit breaker protection
TS
Max. input current
IM (curve C)
16
ITSLJ 1002 - 5964000_04
with a tag board. Ensure that the wire
strands are introduced correctly.
The wiring diagrams are subject to con-
tinuous updating, it is therefore com-
pusory to refer to that on the machine.
To protect the unit against short circu-
its, mount an omnipolar magnet-circuit
breaker protection on the power supply
line (see table), with minimum contact
opening distance of 3mm.
The units require a command panel
(accessory) to be connected as indi-
cated in the wiring diagrams and the
instructions supplied with the command
(IM)
13
16
23
[A]
1
1
1,9
[A]
2
2
3
panel.
The command panel must be compati-
ble with the unit, consult the technical
documentation of the TS unit for selec-
tion.
Each command panel can control just
one unit.
Th e c o m m a n d p a n e l c a n n o t b e
mounted on a metal wall, unles this is
connected to earth permanently .
ATTENTION: check that installation
has been performed correctly. Follow
the control procedures indicated in the
command panel manuals.
34
36
43
46
1,9
1,9
2,6
2,6
3
3
4
4
53
56
63
74
635V
745V
2,6
2,6
3,9
5,5
4
4
6
8
76
765V
5,5
8

Publicité

Table des Matières
loading

Table des Matières