Assistance in the event of faults
8.1
Understanding the LEDs
LEDs on the MultiControl indicate the operating state of the conveyor.
Status description of the LEDs:
• Off: LED is permanently off
• On: LED is permanently on
• Flashes at 1 Hz: LED flashes at a frequency of 1 Hz; duty ratio 1:1
• Flashes at 2 Hz: LED flashes at a frequency of 2 Hz; duty ratio 1:1
• - : LED status is variable
General LEDs
Power
Ready
On
On
-
On
-
-
-
-
-
-
On
On
-
-
Version 2.7 (05/2021) UL
Translation of the original operating manual
Net run
Fault
On
Off
Flashing
Off
1 Hz
-
Flashes x1
-
Flashes x2
-
Flashes x3
-
Flashes x4
-
Flashes x5
Assistance in the event of faults
Meaning
Ready for operation, no error
Bus start-up mode: After starting, the
system waits 30 s for a connection to be
established by the PLC.
Error in the application program, e.g. time
out
Communication error: Connection not
established within 30 s of start-up or
connection to PLC lost. Error acknowledges
itself automatically.
RollerDrive error: Defective RollerDrive
indicated by flashing of the corresponding
"RD" LED
No power supply to motors.
Voltage error, undervoltage
Priority
1
3
2
5
4