2. Installation

2.3.1 Terminal designation

With the IRmax oriented as shown in Diagram 2 on page 4 (M20 cable entry at the
top), the 3-core field cable should be terminated using the removable connector as follows:
+24V at the bottom, 0V in the middle, Signal at the top.
The 6-pin connector on the right of the PCB is for servicing and/or connection of an
IR Display module
+ve terminal:
Sig terminal:
0 V terminal:

2.3.2 Installing IRmax using a mounting bracket

a. IRmax can be supplied with a mounting bracket (S012130) rather than a spigot
gland so that it can be directly connected to field cables (see Diagram 5).
Diagram 5: IRmax with a mounting bracket and cable gland
b. If the IRmax is to be mounted on a flat surface, mark and drill two holes using
the mounting bracket as a template. Loosely fix two parts of the bracket using
fixings suitable for the wall/surface.
c. Remove the weatherproof cap from the IRmax, and slide the body of the IRmax
through the bracket. It is recommended that the IRmax body is installed with the
cable entry facing downwards.
+ve supply from the control card.
Signal/Sense from control card.
-ve supply from the control card.
8
Mounting bracket: 70mm
between fixing centres.
Use M6 bolts