Fault detection and elimination
Error
Cause
Communication
Participant does respond or is
fault during
not available
remote parameter
setting via system
bus (C0370)
(configurable in
C0126)
For operation with application
I/O:
Faulty parameter setting of
parameter set changeover
External fault
A digital input assigned to the
(TRIP−SET)
TRIP−Set function has been
activated.
Communication
Various
abort between
keypad and basic
device
E82ZMV fan
Fan module is defect
module (only 8200
motec
3 ... 7,5 kW)
Fan module is not connected
TRIP or warning
configurable under
C0608
Internal fault
Faulty parameter
Motor not connected
identification
Failure of one/several
Fault in motor
l
phase
motor phase(s)
(is displayed if
Motor current too low
l
C0597 = 1)
Fault in motor
phase
(is displayed if
C0597 = 2)
DC−bus
Mains voltage too low
undervoltage
DC−bus voltage too low
400 V controller connected to
240 V mains
Short circuit
Short circuit
Excessive capacitive charging
current of the motor cable
EDK82MV222 DE/EN/FR 8.0
Fault messages
Remedy
Check whether bus terminator
l
available
Check screen contact of the
l
cables
Check PE connection
l
Check bus load, if necessary,
l
reduce the baud rate
In all parameter sets the signal
"parameter set changeover"
(C0410/13, C0410/14) must be
combined with the same source
Check external encoder
Contact Lenze
Replace fan module
Connect fan module
Check wiring
Contact Lenze
Connect motor
Check motor cables
l
l
Check V
boost
min
Connect motor to
l
corresponding power or adapt
the motor under C0599.
Check mains voltage
Check supply module
Connect controller to the
appropriate mains voltage
Find reason for short circuit;
l
check motor cable
l
Check braking resistor and
cable for braking resistor
Use shorter motor cables with
lower charging current