4
Electrical installation
Mains connection / brake resistor
Fuses and cable cross−sections
Type
mains
E82MV551_4B
3/PE AC
E82MV751_4B
320 ... 550 V;
E82MV152_4B
45 ... 65 Hz
E82MV222_4B
1)
Use UL−approved cables, fuses and fuse holders only.
UL fuse: 500 ... 600 V, tripping characteristic "H", "K5" or "CC"
2)
Pulse−current or universal−current sensitive earth leakage circuit breaker
Observe national and regional regulations
Please observe the following when using e.l.c.bs.:
E.l.c.bs must only be installed between mains supply and controller.
l
Earth leakage circuit breakers can be activated although not required
l
by
– capacitive leakage currents of the cable shields during operation
(especially with long, shielded motor cables),
– simultaneous connection of several controllers to the mains supply.
8200 motec in parallel connection
Type
Mains
current
E82MV551_4B
1.8 A
E82MV751_4B
2.4 A
E82MV152_4B
3.8 A
E82MV222_4B
5.5 A
The sum of mains currents must not exceed 23mA!
1)
IMPORTANT
2)
Observe national and regional regulations
96
Installation to EN 60204−1
Fuse
E.l.c.b.
M6 A
B6 A
M6 A
B6 A
M6 A
B6 A
M10 A
B10 A
Mains contactor required for connection of:
1 motec
2 motec
1)
4 kW
15 kW
2)
4 kW
5.5 kW
Mains contactor determined by inrush currents.
Mains contactor for operation with mains choke 1.5 mH/24 A (order No.
ELN3−0150H024) or current limitation module E82ZJ004 (max. 20 A/phase).
EDK82MV222 DE/EN/FR 8.0
Installation to UL
L1, L2, L3, PE
Fuse
2
[mm
]
1
5 A
1
5 A
1
5 A
1.5
10 A
3 motec
4 motec
1)
1)
15 kW
22 kW
2)
2)
7.5 kW
11 kW
1)
2)
FI
L1, L2, L3, PE
[AWG]
18
18
³ 30 mA
18
16
5 motec
6 motec
1)
1)
22 kW
22 kW
2)
2)
11 kW
11 kW
L
1)
2)