1)
Keypad
PC
−
OU
c
22
OUE
a
75
Pr
a
72
Pr1
a
73
Pr2
a
77
Pr3
a
78
Pr4
a
79
Pr5
a
81
Pt5
a
76
rSt
a
85
sd5
a
87
sd7
a
1)
LECOM−fault number, display in parameter setting program Global Drive Control (GDC)
L
Fault detection and elimination
Error
Cause
DC−bus
Mains voltage too high
overvoltage
(Warning or TRIP
Braking operation
configurable under
C0310)
Earth leakage on the motor
side
Faulty parameter
All parameter sets are
transfer when
defective
using the keypad
Wrong PAR1
PAR1 is defective.
transfer when
using the keypad.
Wrong PAR2
PAR2 is defective.
transfer when
using the keypad.
Wrong PAR3
PAR3 is defective
transfer when
using the keypad.
Wrong PAR4
PAR4 is defective
transfer when
using the keypad.
Internal fault
EEPROM is defective
Time fault during
Data flow from keypad or PC
parameter set
interrupted, e. g. keypad was
transfer
disconnected during transfer
Faulty auto−TRIP
More than 8 fault messages in
reset
10 minutes
Current at analog input < 4
Wire breakage
analog input 1
mA at setpoint range
4 ... 20 mA
Wire breakage
analog input 2
EDK82MV222 DE/EN/FR 8.0
Fault messages
Remedy
Check voltage supply
l
Prolong deceleration times.
Operation with external brake
l
resistor:
– Check dimensioning,
connection and cable of the
brake resistor.
– Increase the deceleration
times
Check motor cable and motor for
earth fault (disconnect motor from
inverter)
It is absolutely necessary to repeat
the data transfer or load the Lenze
setting before enabling the
controller.
Contact Lenze
It is absolutely necessary to repeat
the data transfer or load the Lenze
setting before enabling the
controller.
Depends on the error message
Close circuit at analog input
8
129