SW24.W
PP
OP 2
PP
OP 2
PP
CL 2
-
CL 2
PP
CL 1
LRNA
-
CL 1
OPED
-
CPED
PP
DLOP
PP
DLCL
-
END
Self-calibration:
If the gate travel parameter is changed, there is no need
for the installer to run new calibrations, however, when
changing the travel parameters, the control panel needs
to learn the current curve again, thus disabling the obsta-
cle detection only during the self-calibration manoeuvre.
Self-calibration is appropriately signalled:
- on the control panel display by the code AT
- by the light flashing at twice the normal frequency
The events generating self-calibration are:
- change in parameters: T24, T25, T26, T27, T28, T29,
T30, T31, T32, T33, T34, T35, T40, T41
- loading of settings from a MEM.W memory card
- reset/import of settings from the Wi-Gate app
Start opening motor 2
When button pressed:
slowdown start position on
opening setting.
When button pressed end
of travel position setting or
continuation to the stop.
Start closing motor 2 When
button pressed: slowdown
start position on closing
setting.
Continuation of motor 2
closing at slowdown speed
up to stop.
Start closing motor 1 When
button pressed: slowdown
start position on closing
setting.
Continuation of motor 1
closing at slowdown speed
up to stop.
Start pedestrian opening.
When button pressed:
pedestrian opening posi-
tion setting
Leaf closing from pedes-
trian opening position
Start opening. When
the offset time setting in
opening button is pressed,
motor 2 starts.
Start closing. When the off-
set time setting in closing
button is pressed, motor
1 starts.
End of procedure
Gate travel parameters
S u b
Description
menu
Motor 1 force (%).
Sets the value of the force given to
the motor to push the leaf
T1
Minimum force
Maximum force
Motor 2 force (%).
Sets the value of the force given to
the motor to push the leaf
T2
Minimum force
Maximum force
First leaf to move
T3
Motor 1
Motor 2
Direction.
Sets the motor direction
Standard (a linear motor closes the
gate with pistons extended)
Inverse (a linear motor closes the
T4
gate with pistons retracted)
Note:
Inverts both motors. If only one motor has
an incorrect direction, invert the power
supply wires on the motor with the incorrect
direction.
Number of motors
T6
Single-leaf gate
2 leaf gate
Choice of intervention method
for obstacle detection
Overcurrent or leaf stopped:
the obstacle is detected when the
current threshold or the encoder
slowdown threshold is exceeded
Leaf stopped: the obstacle is
detected only when the leaf slows
T7
down excessively
Overcurrent: the obstacle is de-
tected when the current threshold
is exceeded
Overcurrent and leaf stopped:
the obstacle is detected when the
current threshold and the encoder
slowdown threshold are exceeded
at the same time
Obstacle detection time motor 1
Time after which the current
threshold or the encoder threshold
trigger the obstacle detection for
T10
motor 1 (adjustable at intervals of
100 ms)
100 ms (minimum time)
600 ms (maximum time)
EN
Values
(default)
(50)
1
100
(50)
1
100
(M1)
M1
M2
(1)
1
2
(2)
1
2
(1)
1
2
3
4
(20)
10
60
17