Installation électrique
Protection
Puissance [kW]
A1
A2
A3
A4
A5
B1
B2
B3
B4
C1
C2
C3
9
9
C4
Tableau 9.4 380-500 V, protections de types A, B et C
126
Manuel de configuration
Taille de fusible
recommandée
0.37-1.5
gG-10
0.37-4.0
gG-10 (0,37-3)
gG-16 (4)
5.5-7.5
gG-16
0,37-4
gG-10 (0,37-3)
gG-16 (4)
0.37-7.5
gG-10 (0,37-3)
gG-16 (4-7,5)
11-15
gG-40
18,5-22
gG-50 (18,5)
gG-63 (22)
11-15
gG-40
18,5-30
gG-50 (18,5)
gG-63 (22)
gG-80 (30)
30-45
gG-80 (30)
gG-100 (37)
gG-160 (45)
55-75
aR-200 (55)
aR-250 (75)
37-45
gG-100 (37)
gG-160 (45)
55-75
aR-200 (55)
aR-250 (75)
Danfoss A/S © Rév. 2014-04-04 Tous droits réservés.
Fusible
Disjoncteur
max. recommandé
recommandé Moeller
gG-25
PKZM0-10
gG-25
PKZM0-16
gG-32
PKZM0-25
gG-32
PKZM0-25
gG-32
PKZM0-25
gG-80
PKZM4-63
gG-100
NZMB1-A100
gG-63
PKZM4-50
gG-125
NZMB1-A100
gG-160
NZMB2-A200
aR-250
NZMB2-A250
gG-150 (37)
NZMB2-A200
gG-160 (45)
aR-250
NZMB2-A250
Seuil de déclen-
chement max. [A]
10
16
25
25
25
63
100
50
100
160
250
150
250
MG33BF04