VI - What to do if...? ... Check.
What to do if...?
- No synchronisation after
installation
- The NTP receiver is not
set to the correct time
- The second hand is
stopped on an NTP
receiver clock.
- The unit needs to
be returned to factory
configuration
- There is no DHCP server
on the network
- One of the clocks Profil
does not ignite or makes
restarts in loops.
1) The address and its mode (unicast/multicast) of synchroniza-
tion in the clock correspond to the signal NTP available on the
network.
2) The clock mother spreads(broadcasts) the signal NTP with the
same parameters of synchronization (NTP mode(fashion) + IP
address multicast or unicast).
3) The waiter(server) NTP is on the same network as the receiving
(IP address, mask of network money and footbridges).
4) Absence of PoE (fixed hands): verify the switch PoE.
1) Provoke an immediate research, make a restart of the clock in
the page System of the webserver or disconnect the cable RJ45.
2) The time zone is incorrect.
1) The permanent power supply, which is required for seconds
display, is cut. Check the power supply.
1) Power off the unit
2) Keep the 2 buttons pressed (do not release): pushbuttons on
the clock's circuit board.
3) Power up the unit
4) Wait for the device to reboot a second time
5) Release the buttons
1) By default the clock takes on the following setting (after 3
minutes):
- IP: 172.17.30.110
- MASK: 255.255.0.0
- Gateway: 0.0.0.0
- DNS: 0.0.0.0
2) Use soft BODET Detect PC with the button 'Network
configuration' to define the network parameters of the clock.
3) If no server DHCP, clocks are visible on the software Bodet
Detect (after a starting up, approximately 3 minutes). You can then
configure the address compatible IP / mask with your network.
1) The maximal power of the switch PoE is sufficient to feed all the
clocks connected to the switch.
2) The length of the cable is lower than 100 meters (refer to the
standards of network cabling).
3) All the exits of the switch are compatible PoE.
... Check