Install the fitting on the pipe to comply with the
upstream and downstream distances defined by
standard EN ISO 5167-1 (see Fig. 3).
50 x DN 5 x DN
With control valve
25 x DN 5 x DN
Pipe with 2 elbows
at 90°
18 x DN 5 x DN
With pipe expansion
Fig. 3:
Upstream and downstream distances depending
on the design of the pipes.
English
36
Correct
Correct
Fig. 5:
Additional recommendations on installation
English
38
40 x DN 5 x DN
Pipe with 2 elbows at 90°
in 3 dimensions
20 x DN 5 x DN
Pipe with 1 elbow at 90°
or 1 T-piece
15 x DN 5 x DN
With pipe
reduction
Incorrect
Incorrect
→
Use a flow conditioner, if necessary, to obtain the best
accuracy.
→
Prevent the formation of air bubbles in the pipe (see
Fig. 4).
→
Ensure the pipe is always filled with liquid (see Fig. 5).
Correct
Correct
Direction of fluid flow
Fig. 4:
Additional recommendations on installation
installing a fitting with weld ends
Follow the previously described general installation
recommendations.
note
the seal on the fitting with weld-end connections
may be damaged during welding.
→
Before welding the weld-ends, unscrew the 4 tigh-
tening screws.
→
Remove the sensor holder.
→
Remove the seal.
→
Weld the weld-ends.
→
After welding, correctly replace the seal in the
groove.
→
Replace the sensor holder.
→
Tighten the 4 screws in an alternating pattern, app-
lying a nominal tightening torque of 1,5 Nm.