4.2.3 DIP switches settings with Type 1094 PHR
(Order no. 154463)
Settings for DIP switches S 1-1 through S 1-5 and S 1-8: see 4.2.2
S 1-6
OFF
ON
OFF
ON
Generally, each of the four combinations of dip-switch settings can be used.
With the lowest frequency, the lowest hysteresis is obtained, the PWM
signal, however, is still slightly audible, whereas with the highest frequencies
practically no noise is perceptible.The sensisitivity and hence the excellent
functionality in closed-loop control applications, however, is guaranteed with
all the four frequency settings.

4.2.4 Setting the DIP switches for the 1094 PMR Type

DIP-Switch
S 1
suitable for valve
type
DIP-Switch
S 2
10 - 1094
S1-7
OFF
OFF
ON
ON
low
OFF
2834, 2836, 6023, 6024,
6223 (DN 20)
Zero-point switch-off
aktivated
OFF
Setting at delivery
PWM-Frequency
1000 Hz
1250 Hz
3000 Hz
6000 Hz
PWM-Frequency
medium
ON
2832, 2834, 6022, 6023,
6223 (DN 10, 13)
de-aktivated
ON