Configuring The Overvoltage And Short Circuit Protection In The Critical Load Output; Configuring The Digital Outputs; Configuring The Digital Inputs - Ingeteam INGECON SUN STORAGE 1Play TL M Manuel D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Using the unit
The battery charge power is determined by the lower power between:
Maximum Charge Power.
Difference between the Generator Rated Power and the Consumptions.
18.7.11. Configuring the overvoltage and short circuit protection in the
critical load output
In stand-alone installations and installations connected to the distribution grid with the Battery-backup function
activated, these units can protect the critical load output against overvoltage and short-circuits.
To do this, the following parameters must be set in Configuration > Advanced Settings > Critical Loads Settings.
Setting
Vac L1 Limit
Vac L1 Time
Over-Load in Critical Loads
Short-Circuit in Critical Loads

18.7.12. Configuring the digital outputs

These inverters have several voltage-free outputs which can have the following functionalities:
Options
No Configuration
Start/Stop Generator
On/Off by Communication
On-grid
To configure the digital outputs, go to Configuration > Advanced Settings > Digital Output/Input.

18.7.13. Configuring the digital inputs

These inverters have a DRM0 input for the Australian market and two digital inputs, which can have the following
functions:
Options
No Configuration
Start/Stop Inverter
Connect to Grid
To activate the DRM0 input function, take into account that it should only be configured for use with the DRED
device, required by standard AS4777 (Australia).
If it is configured without the connection of the external DRED device, the inverter will remain stopped.
To configure the digital inputs, go to Configuration > Advanced Settings > Digital Output/Input.
ABH2014IQM01_A - Installation and Operation Manual
Minimum limit of AC voltage that the inverter generates (%Vnom . 10). Below this limit it is
considered an abnormal AC voltage for critical loads.
Time that the AC voltage generated by the inverter must remain under the Vac L1 limit in
order to disconnect the critical loads (ms).
Allows disconnecting the critical loads if an AC overvoltage has been detected 3 times in a
row (see Power 30 min, 2 min, 3 s in
remain stopped until the overvoltage has been removed. Once removed, the inverter must be
reset.
Allows disconnecting the critical loads if an AC short-circuit has been detected 3 times in
a row. By default, the inverter will remain stopped until the fault has been removed. Once
removed, the inverter must be reset.
Description
No task assigned (default option)
Auxiliary generator activation signal
Digital output control via communications.
Signal to indicate that the inverter is connected to
the auxiliary grid or generator.
Description
No task assigned (default option)
Starts or stops the inverter
To connect the inverter to the auxiliary grid or
generator.
Description
"2.4. Specification
table"). By default, the inverter will
State of the normally open (NO) voltage-
free contact
OPEN
Turn off the generator: OPEN
Turn on the generator: CLOSED
Off: OPEN
On: CLOSED
Disconnected: OPEN
Connected: CLOSED
State of the voltage-free contactor /
Voltage level
OPEN / High level
Start: OPEN / High level
Stop: CLOSED / Low level
Do not connect: OPEN / High level
Connect: CLOSED / Low level
Ingeteam
EN
ES
FR
PT
53

Publicité

Table des Matières
loading

Table des Matières