Ingeteam
10.4. Main menu
The main menu contains the following submenus:
Monitoring
Events
Start/Stop
Settings
Advanced settings
Inverter data
To access the various menus and submenus, the desired option must be highlighted over a black background using
the
and
keys and press the
INFO
The menu Advanced settings is password restricted. Access to this menu is only allowed to installers (qualified
personnel). The installer password is 3725.
10.5. Configuring the unit for the first time
The first time that the inverter is powered from the PV array, a series of screens are displayed so as to guide the
inverter's configuration for proper connection to the electric grid.
Follow the instructions on the display. When selecting the country / regulation, select the country in which the
inverter is going to be installed. If the country is not on the list, select Worldwide and select the applicable
regulation. After selecting the regulation, configure the voltage and frequency.
10.6. Configure the string current measurement (INGECON SUN
3Play TL M)
CAUTION
In INGECON SUN 3Play TL, do not perform the configuration described in this section. If configuring the string
current measurement in these cases, it will create warnings on the display.
The unit periodically measures each string and performs a current measurement of all active strings, weighted
to the rated current. Then it calculates the deviation of each string with respect to this weighted average. If the
deviation of one of the strings surpasses the deviation percentage defined by the configuration, this string is
considered to have an anomalous current. If the current of this string is above the deviation percentage defined
during a time greater than that configured for the unit, it generates a current anomaly warning.
The anomalous current detection process starts when the current surpasses the greater of the following two values:
0.5 A or 10% of the strings rated current. The final aim of this starting point is to filter notifications when there is
a very low irradiance or during sunrise or sunset.
To configure the nominal currents of the strings, access the Main menu > Settings > Strings settings.
100
2019-07-09
2019-07-09
This menu includes a series of screens which show the main variables being monitored.
The right-hand screen shows the first one as an example.
This shows the main events such as alarms, warnings and reasons for shutdown.
Start up and shutdown the inverter manually.
Modify parameters to adapt the unit to different operational conditions.
To carry out advanced settings in the inverter. Its access is restricted by the installer
password. Is not user-accessible.
Key data relative to the inverter: serial number, firmware loaded, etc.
key to access it.
10:17
10:17
ABO2011IQM01_C - Installation and Operation Manual
Display control