6 - CONNECTING ADDITIONAL DEVICES

6.1 General wiring diagram - Fig. 20
In order to comply with standard EN 12453, an active edge sensor fitted with
autotest electronics must be installed on the motorisation. After installing
the active edge sensor, it is essential that a stress test be carried out using
measurement equipment which conforms to the requirements set out in clause
5.1.1 of standard EN 12445.
Terminals Terminal
Connection
indication
1
Earth
2
N
Neutral
3
L
Live
4 - 5 - 6
M
Motor
7 - 8
Flash
Orange light output
or 230V - 60W max
zone lighting
9 - 10
Aux
Auxiliary output (dry
contact)
11
Test
Safety test output
12
24 V
24 V accessories
power supply
13
0 V
14
SE
Dry contact
15
Shared
16
Sec Cell - c
Dry contact
17
Sec Cell - o
Dry contact
18
Dry contact
19
Shared
20
Dry contact
21
22
EOS
23
24
Ant.
Conductor
25
Braid
6.2 Description of the various additional devices
Photoelectric cells
• Wiring to "Cell active during opening input" - Fig. 21
(autotest not available during opening)
• Wiring to "Cell active during closing input" - Fig. 22
- With autotest - Dipswitch12 ON
- Without autotest - Dipswitch12 OFF
Reflex photoelectric cell
• Wiring to "Cell active during closing input" with autotest - Fig. 23
230V orange light - Fig. 24
Orange light warning (2 s before the gate starts moving) activated via dipswitch
11.
Aerial - Fig. 25
Keyswitch - Fig. 26
Video doorphones - Fig. 27
Auxiliary contact - lighting - Fig. 28
6
The change in dipswitch status is taken into account immediately.
By default, all dipswitches are OFF.
7.1 Motor torque - Dipswitches 1 and 2
Motor torque
Comments
adjustment
Earth connected in the
factory
230 V power supply
Connected in the
factory
If the "Motor torque setting" is modified, the installer must check that obstacle
Flashing managed by
detection complies with appendix A of standard EN 12 453.
the orange light
Failure to follow this instruction may result in serious injury, e.g. due to crushing
by the gate.
Select lighting or
electric lock with
dipswitch 4
7.2 Motor direction of rotation - Dipswitch 3
Cells active when
DIP - SW 3
closing autotest
OFF
315 mA max for all
accessories on all
ON
outputs
7.3 Auxiliary output - Dipswitch 4
Safety edge
DIP - SW 4
Active during closing
and opening
OFF
ON
Cell active during
closing
7.4 Lighting time delay - Dipswitch 5
Cell active during
DIP - SW 5
opening
OFF
COMPLETE or OPENING
control only input
ON
7.5 Wire input operating modes - Dipswitch 6
PEDESTRIAN or
CLOSING control only
DIP - SW 6
input
OFF
Motor end limit
(connected in the
ON
factory)
7.6 Operating modes - Dipswitches 7 to 9
Aerial
DIP -
SW 7
Sequential
OFF
Sequential + automatic timed close
OFF

7 - ADVANCED PARAMETER SETTING

DIP - SW 1
DIP - SW 2
OFF
OFF
OFF
ON
ON
OFF
ON
ON
WARNING
Setting
Motor installed to the left of the gate
Motor installed to the right of the gate
Setting
Lighting
Electric lock
Setting
30 seconds
120 seconds
Setting
Complete/pedestrian opening control
Opening/closing control
DIP -
DIP -
Setting
SW 8
SW 9
OFF
OFF
Each press on the remote control causes the motor to
move (initial position: gate closed) as per the following
cycle: open, stop, close, stop, open, etc.
OFF
ON
Operation in automatic closing mode is only authorised
if the photoelectric cells are fitted.
In sequential mode with automatic timed close:
- the gate closes automatically after the time delay
programmed with the TIME potentiometer,
- pressing a button on the remote control interrupts
the movement taking place and the timed close (the
gate remains open).
Copyright © 2015 Somfy SAS. All rights reserved.