Types 2030, 2031, 2031 K
→
Loosen fastening screws crosswise and remove actuator
together with diaphragm from the housing.
→
Weld or glue housing into the pipeline.
procedure for control functions B and i
→
Loosen fastening screws crosswise and remove actuator
together with diaphragm from the housing.
→
Weld or glue housing into the pipeline.
Mount actuator and diaphragm on the housing:
→
After welding or gluing in the housing, smooth the housing surface
by grinding if required.
→
Carefully clean the housing.
procedure for control function a
→
Pressurize lower control air connection with compressed air
(value as indicated on the rating plate) (see "Fig. 5: Control air
connection").
→
Place actuator on the housing.
→
Lightly cross-tighten the housing screws until the diaphragm is
between the housing and actuator.
do not tighten the screws yet.
→
Actuate the diaphragm valve twice to position the diaphragm
correctly.
→
Without applying pressure, tighten the housing screws to the
permitted tightening torque (see "Table 9: Tightening torques for
diaphragms").
Installation
→
Pressurize lower control air connection with compressed air (value
as indicated on the rating plate).
→
Check the tightening torque of the screws again.
procedure for actuator with control functions B and i:
→
Place actuator on the housing.
→
Lightly cross-tighten the housing screws without pressurisation
until the diaphragm is between the housing and actuator.
do not tighten the screws yet.
→
Pressurize upper control air connection with compressed air (value
as indicated on the rating plate) (see picture below "Control air
connection").
→
Actuate the diaphragm valve twice.
→
Tighten the housing screws to the permitted tightening torque
(see "Table 9: Tightening torques for diaphragms").
Upper control air connection
(for CFB and CFI)
Lower control air connection
(for CFA and CFI)
Fig. 5:
Control air connection