Normal Operation / Flame Detection Time - Riello GAS 3 Manuel D'entretien

Table des Matières

Publicité

Signal
No blink
The burner does not start 36 - No electrical power supply . . . . . . . . . . . . . . . . . Close all switches - Check connec-
The burner continues to
repeat the start-up cycle,
without lockout
Ignition with pulsations

NORMAL OPERATION / FLAME DETECTION TIME

The control box has a further function to guarantee the correct burner operation (signal: GREEN LED permanently on).
To use this function, wait at least ten seconds from the burner ignition and then press the control box button for a minimum of 3 seconds.
After releasing the button, the GREEN LED starts flashing as shown in the figure below.
GREEN LED on
wait at least 10s
The pulses of the LED constitute a signal spaced by approximately 3 seconds.
The number of pulses will measure the probe DETECTION TIME since the opening of gas valves, according to the following table:
SIGNAL
1 blink
2 blinks
6 blinks
KIT INTERFACE ADAPTER RMG TO PC Code 3002719
Problem
37 - A limiter or safety control device is open. . . . . . . Adjust or replace
38 - Line fuse blocked . . . . . . . . . . . . . . . . . . . . . . . . Replace
39 - Defective control box. . . . . . . . . . . . . . . . . . . . . . Replace
40 - No gas supply . . . . . . . . . . . . . . . . . . . . . . . . . . . Open the manual valves between con-
41 - Mains gas pressure insufficient. . . . . . . . . . . . . . Contact your GAS COMPANY
42 - Minimum gas pressure switch fails to close . . . . Adjust or replace
43 - The gas pressure in the gas mains lies very close
to the value to which the minimum gas pressure
switch has been set. The sudden drop in pres-
sure after valve opening causes temporary open-
ing of the pressure switch itself, the valve
immediately closes and the burner comes to a
halt. Pressure increases again, the pressure
switch closes again and the ignition cycle is
repeated. And so on
44 - Poorly adjusted head . . . . . . . . . . . . . . . . . . . . . Adjust. See page 19
45 - Ignition electrode incorrectly adjusted. . . . . . . . . Adjust, see fig. (C) page 16
46 - Incorrectly adjusted fan air damper: too much air Adjust
47 - Output during ignition phase is too high . . . . . . . Reduce
Press button
for > 3s
FLAME DETECTION TIME
0.4s
0.8s
2.8s
Possible cause
Interval
signal
This is updated in every burner start-up.
Once read, the burner repeats the start-up cycle by briefly
pressing the control box button.
WARNING
If the result is > 2s, ignition will be retarded.
Check the adjustment of the hydraulic brake of the gas
valve, the air damper and the combustion head adjustment.
45
Recommended remedy
tions
tactor and train
Reduce the minimum gas pressure
switch intervention pressure. Replace
the gas filter cartridge.
3s
signal