7.19 Configuration of 1
RELAY CONFIG.
Simple Multicontr.
Run Motor
Simple Multicontr. ⇒ allows to start/stop a constant speed pump
Enable Seq.Ctl.
Synchron. Limit – this will be the stop value of the slave pump
Stop Delay fmin. – this will be the delay time before starting the slave pump.
e.g. if the speed controlled pump reaches the start level, the relay will be switched on,
and will be switched off, when the output frequency falls below the stop level.
Press
on the Hydrovar-Smart to change to

7.20 Submenu Offset

S U B M E N U
Offset

7.20.1 Source of the Offset input

OFFSET INPUT
(Example:)
OFF
EXT ADC-I
the
Note:
If the incoming current signal is below 4mA, there will be an error message on
the display, but no failure is shown (failure relay is not closed). In this case the
OFFSET INPUT works like external signal=0.
EXT ADC-U 0-10V: Offset will be calculated according to the voltage input of 0-
EXT ADC-U 2-10V: Offset will be calculated according to the voltage input of 2-
Press
on the Hydrovar-Smart to change to
st
relay
Selection possible with buttons
⇒ motor run indication (over the relay)
– this will be the start frequency of the slave pump
Press
and the display changes to
The second additional input can be used as required
Off
value 2 and also for an Offset of
the 1
: Offset deactivated
: Offset will be calculated according to the current input (4-20mA) at
terminals X1/12 (X1/10=Ground).
10VDC
at terminals X1/13 (X1/10=Ground)
10VDC
at terminals X1/13 (X1/10=Ground)
for about 3 seconds to enter the submenu
st
required value.
27