If MANUAL CONTROL is selected, the parameter REQUIRED VALUE will change to MANUAL
CONTROL in the main menu, where the actual frequency and the actual value is displayed
(according to the JOG-MODE in the submenu).
Now the frequency can be changed with the
will change with the fasten ramps. After selecting the right frequency, it can be saved with
the standard SAVE.
After a supply failure, the pump will then run with this selected frequency (depending on
the parameter AUTO-START).
The frequency can be changed between the set minimum and maximum frequency.
In the 1
st
display, there is shown the actual frequency.
NOTE:
CONFIG. FMIN will not work in this mode.
Attention
Driving the pump in a not allowed speed range can damage the motor or the
inverter!
Press
on the Hydrovar-Smart to change to

7.16 Control Response

REGULATION MODE
Normal
Press
on the Hydrovar-Smart to change to

7.17 Start Value

START VALUE
disabled
Example:
required value:
start value:
If the pump system have reached the required pressure from 5.0 Bar and there is no more
consumption, the Hydrovar-Smart shuts off the pump. When the consumption increases
and the pressure goes down the pump will normally start. If you have selected the START
VALUE at 2,5 bar the pump will start again at this selected pressure.
Press
on the Hydrovar-Smart to change to
and
buttons, and the speed of the pump
Normal: Speed is increased with falling actual value
signals. (e.g.: Control at constant output pressure).
Inverse: Speed is reduced with falling actual value
signal, (e.g.: Control at constant suction pressure or at
constant level).
This parameter gives you the start value after pump
stop in percentage of the required value (adjustable
between disabled and sensor range).
5,0 bar
2,5 bar
25