Calling Measured Values; Deleting The Measured Value Memory; Reading Out The Measured Value Memory Via The Usb Interface; Printing Measured Values - Benning ST 725 Notice D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

10.2 Calling measured values

-
Press the
-key  to recall the stored measured values with the corresponding storage
location number. The "RECALL" symbol is shown on the display 8 .
-
Press the
-key  again to go to the next storage location.
-
Press the
-key  to go to the previous storage location.

10.3 Deleting the measured value memory

-
Press the
-key  to recall the stored measured values with the corresponding storage
location number. The "RECALL" symbol is shown on the display 8 .
-
To delete the entire measured value memory, press the
the counter reading is reset to zero and "no dAtA" is shown on the display 8 .

10.4 Reading out the measured value memory via the USB interface

To read out the measured values via the USB interface  , you have to install the hardware driver
from the "Treiber-driver" directory on the enclosed CD-ROM and then the download program
from the CD-ROM's "Programm-program" directory on your PC once.
In order to download the data, please proceed as follows:
-
Disconnect all connection cables and test objects from the BENNING ST 725.
-
Connect the BENNING ST 725 to your PC by means of the USB connecting cable.
-
The hardware driver is installed automatically on a free COM port and confirms that the new
hardware can be used.
-
The COM port used can be viewed by means of the Device Manager of your system.
-
Start the "BENNING Datalogger" program, go to "Tools", click "Refresh Ports" and select the
corresponding COM port. Then, click "Download".
-
Press the
-key  of the BENNING ST 725 for approx. 5 seconds until the download
takes place and the entire measured value memory is read out.
-
The measured values can be stored as a (*.csv) or (*.txt) file.
-
Click "Open" to open the measured values e.g. by means of a spreadsheet program.

10.5 Printing measured values

-
To use the print function, connect the optional printer BENNING PT 1 (044150) to the PS2
jack L of the BENNING ST 725 by means of the serial printer cable.
-
As soon as the test sequence is completed and the test result has been called by means of
the
-key , it is possible to print a test document by pressing the
-
The BENNING ST 725 switches the BENNING PT 1 printer on and off automatically with
every print command.
Example of a test certificate

10.6 Setting the date and time

The BENNING ST 725 is equipped with an integrated real-time clock which automatically adds a
date/ time stamp can be added to each storage process.
07/ 2018
Prüfung gemäss DIN VDE 0701-0702
Ident-Nr.
Prüfobjekt
Speicherplatz-Nr.
Datum
Prüfung
Messwert
RPE:
0,10 Ω
RISO:
>19,99 Ω
UISO:
IPE:
< 0,15 mA
Prüfergebnis
Prüffirma
______________________
Prüfer
______________________
BENNING ST 725
__________________
__________________
17.07.2014
Grenzwert
0,3 Ω
1,0 MΩ
500 V
3,50 mA
bestanden
-key  and the
-key  .