Command Set: RTA-RS232 Commands
Command Name
Description
Syntax
Allowed Values
Example
Additional Information
14
RadioTouch
RTA-RS232 Programming and Operation Guide
TM
PS (preset)

Sets the indicated zone to a predetermined preset level

:PS,[zone number],[preset number]<CR>
Zone number: 0 through 9
Preset number: 0 through 16
:PS,6,5<CR> Sets the level for zone 6 to preset level 5
Preset Light Levels: 16 are available with the RS232 interface. Presets 1through 5
correspond to buttons on a RadioTouch wall control (see below) and will take the
RF controller to the same light level as a button press on the wall control. Presets 6
through 8 can be accessed only via the RS232 interface or the RTA-SCI. Presets 9
through16 can be accessed only via the RS232 interface.
Preset 1
Preset 2
Preset 3
Preset 4
RTA-WX-5B
Preset Contact Closures: 5 are available on a RTA-RX-F-SC controller and can be
accessed with the RS232 interface using presets 1 through 5. Contact closure
outputs are primarily used to control Sivoia QED controllable window treatments,
AC motorized shades, and projection screens.
Closure/Preset 2
Closure/Preset 4
Closure/Preset 3
Preset 2
OPEN
Preset 4
STOP
Preset 3
CLOSE
AC Shades
RTA-WX-C3LB
Preset 5
RTA-WX-2B or
RTA-WX-2BSW
RTA-WX-F-SC
Preset 2
UP
Preset 4
DOWN
Projection
Screens
RTA-WX-C2LB
RTA-WX-Q3LB
Note: Press any button (or activate
any preset) when Sivoia QED
shades are moving to stop them
where they are.
ON
OFF
Closure/Preset 1
Closure/Preset 5
Preset 2
OPEN
Preset 4
PRESET
Preset 3
CLOSE
Sivoia QED
Shades