Add A Zone - Lutron Radio Touch RTA-RS232 Guide D'installation Et De Mise En Service

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Programming

Add a Zone

A.Press and hold the CONF and ADDR buttons for 5
seconds to enter unit configuration mode. The LED
display will begin flashing UC to alert you that the
unit has entered unit configuration mode.
B.Press the CONF button repeatedly until the display
shows AS. Press the OK button to begin addressing
zones.
C.To add a zone, press the left scroll button until the
zone number you wish to address is displayed. Press
the ADDR button and the display will show P with
the zone number to be programmed, and the ADDR
LED will turn on.
D.On the RadioTouch controller you wish to add to the
RS232 interface zone, press and release the PROG
button. The lights will cycle up and down for 3
seconds to notify you that you are in programming
mode, and settle at 50% light output. If you are using
an RTA-RX-SW, the lights will cycle off and on. The
Status LED on the controller will be in fast blink
mode. If no lights are connected to this controller,
the status LED will be your only feedback.
E.On the RS232 interface, press and hold the left scroll
and OK buttons for 5 seconds. When the controller
has added the RS232 zone, the lights will flash or
cycle off and on. If no lights are connected to this
controller, hold the buttons until the 3 LEDs around
the display flash (approximately 5 seconds).
Note: To add a zone to an RTA-RS232 interface
shipped before August 2002 (date code K31), press
and hold the right scroll and OK buttons instead.
On the controller, press the PROG button to exit
program mode. The lights will go to high end, and
the STAT LED will return to slow blink mode. If you
are using an RTA-RX-SW, the lights will cycle off and
on.
Repeat these steps for any other controllers that
should be controlled by this zone of the RS232
interface.
Press and hold the CONF and ADDR buttons for 5
seconds to exit unit configuration mode. The display
will start to sequence (approximately 5 seconds).
RadioTouch
R
A
TX
RX
Press and hold for 5 seconds to enter or exit unit
configuration mode.
B
TX
RX
Press CONF until the LED
display reads AS.
C
TX
RX
Press the left scroll button
to display the desired zone
number.
D
R adio T ouch
120/277 V
60 Hz
TM
16 A Max.
RT A-RX-F
LISTED 243C
I nd . C ont . E q .
Coopersburg, PA 18036 USA
Refer to the Installers Guide for more
detailed instructions.
1-800-523-9466
Consulte la Guía de Instaladores para
USA, Canada
información más detallada.
1-888-235-2910
Mexico
Référer au Guide d'installation pour plus de
www.lutron.com
renseignements détaillés.
CONFIGURACIONES
REGLAGES
SETTINGS
PWR
STAT
PROG
ON
1
2
3
4
5
1 2
3
4 5 6 7 8
0-10
®
V
ON
1
2
3
4
5
1
2
3
4
5
6
7
8
E
TX
RX
Press and hold the left scroll and OK buttons on the
interface for 5 seconds.
RTA-RS232 Programming and Operation Guide
TM
Then press OK.
Press ADDR to display P
in the left window and
light the ADDR LED.
®
100 H r /100%
RadioTouch controller
(this step only)
PROG button
Status LED