Installation
2.7
Information on refrigerant
This device contains fluorinated greenhouse gases as refrigerant. The
unit is hermetically sealed. The following information on the refrigerant
complies with the requirements of EU Regulation No. 517/2014 on
fluorinated greenhouse gases.
Outdoor Unit Rated cooling
output
[kW]
CL7000i 20 E
2.0
CL7000i 26 E
2.5
CL7000i 35 E
3.4
CL7000i 41 E
4.0
CL7000i 53 E
5.0
Table 6 F-Gas
If the distance between the indoor and outdoor units exceeds 5 meters,
additional refrigerant charge must be added. For every meter of
additional distance, it is necessary to include an extra 12 grams of
refrigerant charge.
3
Installation
3.1
Before installation
CAUTION
Risk of injury from sharp edges!
▶ Wear protective gloves during installation.
CAUTION
Danger of burns!
During operation the pipes become hot.
▶ Make sure, that the pipes cooled down before touching them.
▶ Check the scope of delivery for damage.
▶ Check whether a hissing sound due to negative pressure can be
detected when opening the pipes of the indoor unit.
3.2
Requirements for installation site
▶ Observe minimum clearances ( Figures 4 toand to add to this).
Indoor Unit
▶ Do not install the indoor unit in a room in which open ignition sources
(for example: open flames, an operating wall mounted gas boiler or
an operating electric heating system) are in operation.
▶ The installation location must not be higher than 2000 m above sea
level.
▶ Keep the air inlet and air outlet clear of any obstacles to allow the air
to circulate freely. Otherwise poor performance and higher noise
levels may occur.
70
Rated heating
Refrigerant
output
Type
[kW]
3.5
R32
4.1
R32
4.1
R32
4.6
R32
5.5
R32
Information for the installer: If you refill refrigerant, enter the additional
charge size and the total charge size of the refrigerant in the table
"information on refrigerant" below.
Global
CO
2
Warming
equivalent of
Potential
initial charge
(GWP)
[metric tons]
eq.]
[kgCo
2
675
0.57
675
0.61
675
0.61
675
0.68
675
0.84
2.8
Product information on electrical connection
including radio equipment components
Please refer to chapter 3.10.
In order to select the correct fuse for this installation, it is important that
the skilled person installing the air conditioner pays attention to chapter
3.9.
▶ Keep TV, radio and and similar appliances at least 1 m away from the
unit and the remote control.
▶ Mount the indoor unit on a wall that absorbs vibrations.
▶ Take minimum room area into account
Indoor Unit
CL7000iU W 20 E
CL7000iU W 26 E
CL7000iU W 35 E
CL7000iU W 41 E
CL7000iU W 53 E
Table 7 Minimum room area
If the installation height is lower, the floor area must be accordingly larger.
Outdoor Unit
▶ The outdoor unit must not be exposed to machine oil vapour, hot
spring vapour, sulphur gas, etc.
▶ Do not install the outdoor unit directly next to water or where it is
exposed to sea air.
▶ The outdoor unit must always be kept free of snow.
▶ There must be no disruption caused by extract air or operating noise.
▶ Air should be able to circulate freely around the outdoor unit, but the
appliance must not be exposed to strong wind.
▶ Condensate that forms during operation must be able to drain off
easily. Lay a drain hose if required. In cold regions, installation of a
drain hose is not advisable as it could freeze.
▶ Place the outdoor unit on a stable base.
Initial charge
Additional fill
volume [kg]
volume [kg]
0.85
(Pipe length-5)
*0.012
0.90
(Pipe length-5)
*0.012
0.90
(Pipe length-5)
*0.012
1.00
(Pipe length-5)
*0.012
1.25
(Pipe length-5)
*0.012
Installation height
Minimum room area
[m]
≥ 1.8
Climate 7000i – 6721873506 (2024/12)
Total charge
volume during
commissioning
[kg]
2
[m
]
≥ 4